No.
Part name
Pulse motor
1. Detachment
9
valve coil
1) Perform step 1. in
2) Release the coil from the notch by turning it,
2. Attachment
1) Put the coil deep into the bottom position.
2) Fix the coil firmly by turning it to the notch
The pulse motor valve has A, B and C room
side.
After mounting it, check that coil at B room
side (Nothing is marked on the pulse motor
valve.) is connected to CN702.
Check that coil at C room side (Red marking
is marked on the pulse motor valve.) is
connected to CN703 of the control board
assembly respectively.
10
Fan guard
1. Detachment
1) Perform work of item 1 of
2) Remove the front cabinet, and put it down so
Perform work on a corrugated cardboard,
cloth, etc. to prevent flaw to the product.
3) Remove the hooking claws by pushing minus
2. Attachment
1) Insert claw of the fan guard in the hole of the
All the attaching works have completed.
Check that all the hooking claws are fixed to
the specified positions.
Procedure
, all the steps in
2
5
in
.
and remove coil from the pulse motor valve.
position.
that fan guard side directs downward.
screwdriver according to the arrow mark in the
right figure, and remove the fan guard.
front cabinet.
Push the hooking claws (12 positions) by
hands and fix the claws.
– 107 –
and 1.
3
Set the positioning bracket on the
PMV coil to a concavity at PMV
unit side and fix PMV coil. In this
time, match color of ID mark at
the coil side with that of ID mark
at the PMV unit side. Make sure
also that pipes do not deform
when inserting and fixing the coil.
1
and 1 of
2
.
Remarks
PMV coil
Positioning bracket
at coil side
Lead wire
take-out port
ID mark
Positioning concavity
at PMV unit side
(72˚ pitch)
ID mark
PMV unit
MountMounting Method of
Pulse Motor Valve (PMV) Coil
Minus screwdriver
Hooking claw