No.
Part name
TE sensor (outdoor heat exchanging temperature sensor)
11
• Attachment
With the sensor leads pointing in the direction shown in the
figure, install the sensor onto the straight pipe part of the
condenser output pipe.
12
TS sensor (Suction pipe temperature sensor)
• Attachment
With its leads pointing downward, point the sensor in the
direction of the packed valve, and install it onto the straight
pipe part of the suction pipe.
TD sensor (Discharge pipe temperature sensor)
13
• Attachment
With its leads pointed downward, install the sensor facing
dowmward onto the vertical straight pipe part of the discharge
pipe.
TO sensor (Outside air temperature sensor)
14
• Attachment
Insert the outdoor air temperature sensor into the holder, and
install the holder onto the heat exchanger.
15
TGa/TGb/TGc sensor (Gas side pipe temperature sensor)
• Attachment
With its leads pointing downward, point the sensor in the
direction of the front cabinet, and install the sensor onto the
straight pipe part of gas side pipe. Match the sensor protective
tube colors with the pipe marking colors and install the
sensors. TGa is yellow, TGb is not marking color, and TGc is
green.
During the installation work (and on its completion), take care not to damage the
coverings of the sensor leads on the edges of the metal plates or other parts. It is
dangerous for these coverings to be damaged since damage may cause electric
shocks and/or a fire.
After replacing the parts, check whether the positions where the sensors were installed are
the proper positions as instructed. The product will not be controlled properly and trouble will
result if the sensors have not been installed in their proper positions.
Procedure
CAUTION
– 108 –
Remarks
• Shown in the above figure is the
model 3M18SAV-E.
TS
TD
TGc
TGb
TGa
TO
TE