8
Start-up procedure
Push against the drawer (fig. 40) to close the control
panel.
8.13 Testing the Ignition Safety shut off
device
Switch off the heating system using the main switch.
Disconnect the plug and socket connection of the moni-
toring cable.
Switch on the heating system using the main switch.
Press the "Chimney Sweep"
approx. two seconds), until the display shows the
decimal point.
Check if the boiler does one start-up attempt and three
restart attampts.
After each start-up attempt the boiler will signal a start-up
failure. A "6A" code can be seen in the display.
After the last start-up attempt, the boiler will lock out. The
"6A" code is blinking in the display.
Connect the plug and socket connection of the moni-
toring cable.
Press the reset button.
Check if the boiler starts-up.
Press the "Chimney Sweep" button return to normal
operating conditions.
8.14 Installing the casing
Install the casing and close the latches (fig. 41).
Do not lift the casing by the latches!
Lock the latches using the radiator key.
8.15 Informing the owner, handing over the
technical documents
Show the owner how the heating system works and how
the boiler can be operated. Hand over the technical
documents.
38
Logamax plus GB142-24/30/45/60 - We reserve the right to make any changes due to technical modifications!
d
button and hold it (for
Fig. 40 Closing the control panel
Fig. 41 Installing the casing