Switch off the heating system using the main switch.
Dismantle the boiler again and flush the heat exchanger
with water.
Pull the condensate trap from the condensate plate
(fig. 48, pos. 1).
Pull the internal condens bypass pipe from the conden-
sate trap (fig. 48, pos. 2).
Loosen the condensate trap from the connection (fig. 48,
pos. 3) and remove it.
Use a bristle brush to clean the condensate trap.
Flush the condensate trap.
Fill the condensate trap with water before re-installing it.
Check the condensate trap gasket for damage and
replace it if necessary.
Re-assemble all parts in reverse order of disassembly.
12.2 Checking and adjusting the gas/air-ratio
See chapter 8.8 "Checking and adjusting the gas/air ratio",
page 34.