12 Maintenance
CAUTION
There is no need to lubricate the combustion
motor as it is permanently lubricated.
Switch off the heating system using the main switch.
Close the gas shut-off valve.
Remove the casing.
12.1 Cleaning the heat exchanger, burner
and condensate trap
CAUTION
To avoid a short circuit.
– Do not spray the cleaning agent onto the
burner, the hot surface ignitor, the ionization
electrode or other electric components.
Dismantle the hot surface ignitor and the ionization elec-
trode.
Loosen the fastening nuts (fig. 43, pos. 1).
Remove the earth cable (fig. 43, pos. 2).
Remove the retaining plate.
Pull the hot surface ignitor (fig. 43, pos. 3) and the ioniza-
tion electrode (fig. 43, pos. 4) out of the heat exchanger.
Loosen the threaded connection to the gas control valve
(fig. 44, pos. 1) and pull the plug (fig. 44, pos. 2) from the
gas valve terminal block.
Pull the plug from the fan unit (fig. 44, pos. 3).