Anytime cycle sequence is modified, softener set-up will revert to
manufacturer setting and must be reprogrammed as desired.
Cycle Sequence instructions allows the operator to set the order of the
cycle. The Softener System Setup allows the operator to set how long
the cycles will last. The operator may choose up to 9 cycles in any order.
END must be used as the last cycle option. The SERVICE cycle should
only be used in brine prefill applications to allow salt to dissolve.
The following is an example of how to set a valve so that when regeneration is initiated, BACKWASH occurs first, REGENERANT
DRAW DN occurs second, RINSE occurs third, and FILL occurs fourth.
1.5
SET
AUX VALVE CONTROL
OFF
SET
RECLAMATION MODE
ENABLED
SET
RECLAIM START
30:00
MIN
SET
RECLAIM DURATION
8:00
MIN
SET
17

CYCle seQuenCe

STEP 1 CS – Press NEXT and  simultaneously for three seconds and release. Then press
Step 1CS
NEXT and  simultaneously again for 3 seconds and release. If screen in step 2CS does not ap-
pear in 5 seconds the lock on the valve is activated.
STEP 2 CS – Meter Size. Use the  or  to select from 1.0", 1.25", 1.50", 2.0" meter. H150 is
Step 2CS
a 1.5" meter. It is necessary to select meter size to coincide with control valve size used. Press
NEXT to go to Step 3C.
STEP 3CS – Use the  or  to select on of the following:
Step 3CS
• OFF; or
• Brine Reclaim – Step 4CS; or
• Twin Alternating – Step 6CS System; or
• No Hard Water Bypass During Regeneration – Step 7CS.
• Factory Setting is OFF
Only displays if reclamation of brine is enabled in Step 3CS. Selection requires that a connection
to a MAV is made to the two-pin connector labeled drive on PC board.
STEP 4CS – Use the  or  buttons to select the number of minutes after the start of the draw
Step 4CS
cycle before the MAV will divert the brine waste water from the plumbing drain receptacle to the
brine tank.
Press NEXT to go to Step 5CS. Press REGEN to return to previous step.
STEP 5CS – Only displays if reclamation of brine is enabled in Step 3CS. Use the  or  buttons
Step 5CS
to select the number of minutes to divert the brine waste water to the brine tank. After the minutes
count down to zero the waste water will once again be diverted to the plumbing drain receptacle.
Press NEXT to go to Step 8CS. Press REGEN to return to previous step.
Cycle Options
REGENERANT
BACKWASH
DRAW-DN
RINSE
SOFTENING
FILL
END