DELAY + IMMEDIATE
Step 12S
REGEN
SET
RELAY 1 TRIGGER
Step 13S
TIME
SET
RELAY 1 SET POINT
Step 14S
10:00
SET
MIN
RELAY 1 DURATION
Step 15S
3:00
MIN
SET
RELAY 1 TRIGGER
GALLONS
SET
RELAY 1 SETPOINT
Step 16S
1
SET
GAL
RELAY 1 DURATION
Step 17S
0:01
MIN
SET
Figure 12b
13
STEP 12 S – Set Regeneration Time Options using the  or  button. If value is set to:
• "DELAY" means regeneration will occur at the preset time;
• "IMMEDIATE" means regeneration will occur immediately when the gallons capacity reaches 0
(zero); or
• "DELAY + IMMEDIATE" means regeneration will occur at one of the following:
- the preset time when the gallons capacity falls below the reserve or the specified number of days
between regenerations is reached, whichever comes first; or
- immediately after 10 minutes of no water usage when the gallon capacity reaches 0 (zero).
See page 34 for more options. Factory Setting is DELAY + IMMEDIATE. Press NEXT to go to
Step 13S. Press REGEN to return to previous step.
STEP 13 S – Set Relay to activate by Time or Gallons, REGEN GALLONS or OFF by using 
or  buttons. A relay can be used to operate a chemical feed pump or solenoid. The choices are:
• Relay Triggered on Time - Relay activates after set number of minutes after start of regenera-
tion. Start of regeneration is defined by first backwash cycle, dn brine or up brine, whichever
is first. Relay deactivates after set time.
• Relay Triggered on Gallons - Relay activates every set number of gallons while in service and
deactivates after set time.
• Regen Gallons - Relay activates after set number of gallons in service or water used during
regeneration and de-activates after set time or when meter stops registering flow, whichever
comes first.
• Off - If off is selected, Steps 14S or 15S will not be shown. Factory setting = OFF. Press
NEXT to go to step 14S or 15S for relay settings, or 20S if OFF selected.
STEP 14 S – If off was selected in previous step, this screen does not appear.
If Time chosen to Activate Relay, use up and down arrows to set # of minutes AFTER START OF
REGEN to activate relay. Press NEXT.
Start of regeneration is defined as first Backwash or Regenerant Draw.
STEP 15 S – Use Up and Down arrows to set duration of relay activation in minutes.
Time Range = 1 second - 500 minutes. Press NEXT to go to second relay programming. Press
REGEN to return to previous step.
Relay set to be triggered on gallons. If Off or Time was selected in previous steps, this screen
does not appear.
STEP 16 S – If Gallons Chosen to Activate Relay, use up and down arrows to set # of gallons
per relay activation. Range = 1-100 gallons. Press NEXT to set duration of relay activation.
STEP 17 S – Use up and down arrows to set duration of relay activation in minutes. Range = 1
second - 500 minutes. Press NEXT to go to second relay programming. Press REGEN to return
to previous step.