7. Exhaust Pipe Location

IT IS RESPONSABILITY OF THE HOMEOWNER TO KEEP THE VENT
NOTE:
USE ONLY LISTED COMPONENTS SUPPLIED WITH THE BOILER.
SURFACE DISCOLORATION OF THE BUILDING MAY OCCUR DUE TO
IMPROPER INSTALLATION. QHT WILL NOT ACCEPT RESPONSIBILITY OR
LIABILITY FOR SUCH DISCOLORATION.
The Exhaust Hood must be installed on the leeward side of house and conform to the
following guidelines:
1. The Vent hood shall not be less than 3 feet above any forced air inlet to the house.
2. The Vent hood shall not be less than 4 feet below, 1 foot horizontally, or 1 foot above any
door, window or gravity inlet into any building.
3. The Vent hood shall not be less than 2 feet from an adjacent building.
4. The Vent hood shall be not less than 7 feet above grade when located adjacent to public
walkway.
5. The Vent hood shall be located so that flue gasses are not directed to jeopardize people,
overheat combustible structures, materials or enter buildings.
6. Minimum of 6 feet horizontal clearance from electric meters, gas meters, regulators and
relief equipment.
7. All joints in system are to be sealed to prevent leakage of products of combustion
in the building.
Avoid installing exhaust hood on the North, West, or the side of the house receiving the
8.
prevailing winds.