System Messages
Number
150000
No more data is read or written.
This can have various causes:
The cable is defective.
The PLC does not respond, is defective, etc.
Connection made to the wrong interface.
The system is overloaded.
150001
Connection is re-established because the cause of
the interruption has been eliminated.
160000
No more data is read or written.
This can have various causes:
The cable is defective.
The PLC does not respond, is defective, etc.
Connection made to the wrong interfacet.
The system is overloaded.
160001
Connection is re-established because the cause of
the interruption has been eliminated.
1)
170000
S7 diagnostics messages are not displayed because
it is not possible to logon to the S7 diagnostics with
this unit. The service program is not supported.
1)
170001
The S7 diagnostics buffer cannot be displayed
because communication with the PLC has been
switched off.
1)
170002
The S7 diagnostics buffer cannot be displayed
because reading in the diagnostics buffer (SZL) was
terminated due to an error.
1)
170003
The display of an S7 diagnostics message is not
possible. An internal error %2 has been reported.
1)
170004
The display of an S7 diagnostics message is not
possible. An internal error with error class %2, error
number %3 has been reported.
1)
170007
It is not possible to read in the S7 diagnostics buffer
(SZL) because it was terminated with an internal error
with error class %2 and error code %3.
180000
A component/OCX receives configuration data with a
version identification which is not supported.
190000
It is possible that the tag will not be updated.
190001
The tag is updated following an error status after the
cause of the last error state has been eliminated
(return to normal operation).
190002
The tag is not updated because communication to the
PLC has been switched off.
190004
The tag is not updated because the configured
address is not available for this tag .
190005
The tag is not updated because the configured PLC
type does not exist for this tag .
C-8
Effect/Cause
Remedy
Check that the cable is plugged in,
the PLC is operational, the correct
interface is used.
Reboot the system if the system
message is displayed
continuously.
Check that the cable is plugged in,
the PLC is operational, the correct
interface is used.
Reboot the system if the system
message is displayed
continuously.
Switch the PLC online.
Install a newer component.
Switch on communication via the
function "Set Online".
Check the configuration.
Check the configuration.
MP270 Equipment Manual
Release 01/99