Number
80006
Since archiving is not possible, this causes a
permanent loss of the functionality.
80008
Since archiving is not possible, this causes a
permanent loss of the functionality.
80010
Since the path was incorrectly entered in ProTool, this
causes a permanent loss of the functionality.
80011
Target archives are open.
80012
Archive values are stored in a buffer. If the values are
read to the buffer faster than they can be physically
written (e.g. using a hard disk), overloading may occur
and recording is then stopped.
80013
The overload status no longer applies. Archiving
resumes the recording of all values.
80014
The same action was triggered twice in quick
succession. Since the process is already in operation,
the action is only carried out once.
110000
The operating mode status has been changed. The
operating mode is now offline.
110001
The operating mode status has been changed. The
operating mode is now online.
110002
The operating mode status has not been changed.
120000
The trend is not displayed because an incorrect axis
to the trend, or incorrect trend, has been configured.
120001
The trend is not displayed because an incorrect axis
to the trend, or incorrect trend, has been configured.
120002
The trend is not displayed because the tag assigned
tries to access an invalid PLC address.
130000
The action was not executed.
130001
The action was not executed.
130002
The action was not executed.
MP270 Equipment Manual
Release 01/99
Effect/Cause
System Messages
Remedy
In the case of databases, check
whether the corresponding data
source exists and start up the
system again.
Restart the system when the full
functionality is required.
Configure the path for the
respective archive again and
restart the system when the full
functionality is required.
You have two minutes in which to
close the target archive, then a
new attempt is made.
Archive less values.
Or increase the recording interval.
Check the connection to the PLCs.
Check whether the address area
for the area pointer "Coordination"
in the PLC is available.
Change the configuration.
Change the configuration.
Check whether the data area for
the tag exists in the PLC, the
configured address is correct or
the value range for the tag is
correct.
Close other applications.
Delete files no longer required from
the hard disk.
Delete files no longer required from
the hard disk.
Close other applications.
Delete files no longer required from
the hard disk.
C-5