Number
140008
No tag updating or writing is executed because the
configuration data is incorrect:
The following parameters could not be entered in the
registry:
0:
General errors
1:
Incorrect version
2:
Profile cannot be entered in the registry.
3:
Sub-network type cannot be entered in the
registry.
4:
Target rotation time cannot be entered in the
registry.
5:
Highest addresse (HSA) incorrect.
140009
No tag updating or writing is executed because the
module for the S7 communication was not found.
140010
No S7 communication peer could be found because
the PLC is switched off.
DP/T: The option "Is not active as the only master" is
set in the Control Panel under "Set PG/PC interface".
140011
No tag updating or writing is executed because
communication is interrupted.
140012
There is an initialization problem (e.g. when
ProTool/Pro RT has been terminated in the Task
Manager).
Or: another application (e.g. STEP7, WINCC) is active
with different bus parameters and the driver cannot be
started with the new bus parameters (e.g. baud rate).
140013
The MPI cable is not plugged in and, thus, there is no
power supply.
140014
140015
Incorrect baud rate
Or: incorrect bus parameter (e.g. HSA)
Or: OP address > HSA
Or: incorrect interrupt vector (interrupt does not arrive
at the driver)
140016
140017
MP270 Equipment Manual
Release 01/99
Effect/Cause
System Messages
Remedy
Check the connection and whether
the PLC is switched on.
Check the parameter definitions in
the Control Panel using "Set
PU/PC interface".
Restart the system.
Re-install the module in the Control
Panel using "Set PG/PC interface".
Switch the PLC on.
DP/T:
If only one master is connected to
the network, deactivate the option
"Is not active as the only master" in
"Set PG/PC interface".
If the network has more than one
master, switch this master on. Do
not modify any settings here,
otherwise a bus fault may occur.
Check the connection and that the
communication peer is switched
on.
Restart the operating unit.
Or start ProTool/Pro RT first and
then the other applications.
Check the connections.
In the configuration modify the
operating unit address.
Correct the incorrect parameters.
Change the interrupt number.
Change the interrupt number.