Maintenance
Remove the baffle plate and clean it using
compressed air (fig. 40).
Flush the heat exchanger with water.
Re-assemble all parts in reverse order of
disassembly.
NOTE
It is important to inspect and properly replace
the rubber gaskets.
Switch on the heating system using the main switch.
Press the "Chimney Sweep"
decimal point is displayed. Leave the appliance on
for approx. 10 minutes.
Switch off the heating system using the main switch.
Dismantle the appliance again and flush the heat
exchanger with water.
Pull the condensate trap from the condensate plate
(fig. 42, pos. 1).
Loosen the condensate trap from the connection
(fig. 42, pos. 2) and remove it.
Flush the condensate trap.
Fill the condensate trap with water before
re-installing it.
Loosen the retaining clips (fig. 38, pos. 5, page 46)
on the condensate trap and remove the condensate
trap.
Use a bristle brush to clean the condensate trap.
Check the condensate trap gasket for damage and
replace it if necessary.
Re-assemble all parts in reverse order of
disassembly.
We reserve the right to make any changes due to technical modifications!
Installation and Servicing Instructions Logamax plus GB142-24/30/45/60 • Version 12/2004
button until the
Fig. 40 Baffle plate
1
Fig. 41 Cleaning the heat exchanger
2
Fig. 42 Condensate trap
Buderus Hydronic Systems • http://www.buderus.net
13