12  Technical Data

12 Technical Data

12.1 DC⁄AC

12.1.1 Sunny Boy 3000-US

DC input
Maximum MPP voltage at 208 V nominal value
Maximum MPP voltage at 240 V nominal value
Input operating voltage range
Maximum PV array input power
Maximum DC power
DC start voltage
Maximum DC input current
Maximum short-circuit current
DC voltage ripple
AC output
AC operating voltage range at 208 V nominal value
AC operating voltage range at 240 V nominal value
AC operating frequency range
AC frequency, nominal value
Maximum continuous AC output power
Total harmonic factor of the output current with total
harmonic factor of the AC voltage ˂ 2%
and AC power ˃ 50% rated power
Maximum continuous AC output current at 208 V
Maximum continuous AC output current at 240 V
Maximum residual output current
Maximum output overcurrent protection
Maximum backfeed current from the power distribution
grid to the PV array
Synchronization of inrush current
Tripping limit accuracy
Tripping time accuracy
90
SB30-40-US-IA-en-33
SMA America, LLC
180 V to 400 V
200 V to 400 V
200 V to 500 V
3,750 W
3,250 W
230 V
17 A
24 A
˂ 10%
183 V to 229 V
211 V to 264 V
59.3 Hz to 60.5 Hz
60 Hz
3,000 W
˂ 4%
15 A
13 A
30 A
30 A
30 A AC
8 A
− 2% to +2%
− 0.1% to +0.1%
Installation Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents