10  Troubleshooting
Name
Description
Fac-delta+*
Maximum permissible
frequency deviation
above the power
frequency of 60 Hz
before the grid monitoring
disconnects the device
from the power
distribution grid.
The standard value is
optimal for plants
˂ 30 kW.
Fac-MinTripTime* Switch-off time having
fallen below power
frequency.
The standard value is
optimal for plants ˂30 kW.
Fan-Test
By setting this parameter
to 1, you can check the
function of the fan.
h_total
Total operating hours of
the inverter.
It may be necessary to
change this if you replace
your inverter and want to
use data from the old
device.
68
SB30-40-US-IA-en-33
Value/range
0 Hz to 4.5 Hz
0.16 s to 300 s
1
The fan is set to
the maximum
speed.
0
Operating
mode: OptiCool
0 h to 200,000 h
SMA America, LLC
Explanation
Default
value
0.49 Hz
(for the
country
setting USA/
UL1741/
2005)
0.16 s
Installation Manual
0
0 h