SMA SUNNY BOY 3000-US Installation Manual page 67

Pv inverter
Hide thumbs Also See for SUNNY BOY 3000-US:
Table of Contents

Advertisement

SMA America, LLC
Name
Description
CO2-Fact
The inverter assesses the
yield and displays the
approximate amount of
CO
saved.
The amount of CO
calculated by multiplying
the generated kWh
(E-total) by the factor
defined in the parameter
"CO2".
Default
Defines the country
standard for adjusting
country-specific
information. Tip: After
changing one of the
parameters marked with
"*", the parameter
"Default" automatically
changes to adjusted.
E_total
Total energy yield of the
inverter.
It may be necessary to
change this if you replace
your inverter and want to
use data from the old
device.
Fac-delta–*
Maximum permissible
frequency deviation below
the power frequency of
60 Hz before the grid
monitoring disconnects the
device from the power
distribution grid. The
standard value is optimal
for plants ˂ 30 kW.
Installation Manual
that the inverter has
2
is
2
Value/range
0 lb./kWh to 2 lb./
kWh
USA/UL1741/
2005
OFF_Grid
NON IEEE1547
0 kWh to
200,000 kWh
0.2 Hz to 3.0 Hz
10  Troubleshooting
Explanation
Default
value
1.7 lb./kWh
USA/
UL1741/
2005
0 kWh
0.69 Hz
(for the
country
setting USA/
UL1741/
2005)
SB30-40-US-IA-en-33
67

Hide quick links:

Advertisement

Table of Contents
loading