Toshiba RAV-SM567CTP-E (TR) Service Manual page 63

Split type indoor unit ceiling type
Hide thumbs Also See for RAV-SM567CTP-E (TR):
Table of Contents

Advertisement

DN
01
Filter sign lighting time
02
Filter pollution leve
03
Central control address
06
Heating suction temperature shift
0F
Cooling only
10
Type
11
Indoor unit capacity
12
System address
13
Indoor unit address
14
Group address
19
Louver type (wind direction adjustment)
Temperature range of cooling/heating
1E
automatic SW control point
28
Power failure automatic recovery
2b
Thermo output SW (T10
31
Ventilation fan (standalone)
32
Sensor SW (Selection of static pressure)
5d
High ceiling SW
60
Timer setting (wired remote controller)
Demand setting
C2
(outdoor unit current demand)
d0
Remote controller operation save function
d3
Rotation number of the self-clean operation
d1
Frost protection function
F6
Presence of Application control kit
Table 2. Type: CODE No. 10
Setting data
0001∗1
4-way Cassette Type
0007∗2
∗ ∗ 1 EEPROM initial value on the P .C. board for
indoor unit servicing.
∗2
CAUTION
<Model name: RAV-SM∗∗∗CTP∗>
For above models, set the CODE No. to "
"0000" (initial) to "0001".
Table 1. Setting data (CODE No. table (example))
Item
3
)
Type
Ceiling Type
" and the setting data
Setting data
Depending on Type
0000: standard
0099: Not determined
0002: +2°C
(flooring installation type: 0)
0000: Heat pump
Depending on model type
Depending on capacity type
0099: Not determined
0099: Not determined
0099: Not determined
Depending on Type.
0003: 3 deg (Ts±1.5)
0000: None
0000: Thermo ON
0000: Not available
0000: Body sensor
0000: Standard
0000: Available
0075: 75 %
0001: Enable
0000: None
0000: None
0000: None
Indoor unit capacity: CODE No. 11
Type name abb.
RAV-SM∗∗∗UT∗
RAV-SM∗∗∗CTP∗
∗ EEPROM initial value on the P .C. board
– 63 –
FILE NO. SVM-13050
Factory-set value
Table 3.
Setting data
0000∗
0009
0012
0015
0017
0018
for indoor unit servicing.
Type
Disable
56
80
110
140
160