Toshiba RAV-SM567CTP-E (TR) Service Manual page 55

Split type indoor unit ceiling type
Hide thumbs Also See for RAV-SM567CTP-E (TR):
Table of Contents

Advertisement

[F02 error]
Is connection of TC sensor connector
(CN101 on Indoor P.C. board) correct?
YES
Are characteristics of
TC sensor resistance value normal?
YES
Check indoor P.C. board (MCC-1643).
Defect → Replace
[F01 error]
Is connection of TCJ sensor connector
(CN102 on Indoor P.C. board) correct?
YES
Are characteristics of
TCJ sensor resistance value normal?
YES
Check indoor main P.C. board (MCC-1643).
Defect → Replace
NO
NO
∗ Refer to Characteristics-2.
NO
NO
∗ Refer to TCJ sensor
(Temperature-Resistance value characteristic table)
Correct connection of connector.
Correct connection of connector.
– 55 –
FILE NO. SVM-13050
Replace TC sensor.
Replace TCJ sensor.