Systematic Refrigerating Cycle Diagram - Toshiba RAV-SM567CTP-E (TR) Service Manual

Split type indoor unit ceiling type
Hide thumbs Also See for RAV-SM567CTP-E (TR):
Table of Contents

Advertisement

2. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM

2-1. Indoor Unit
• Single type (Combination of 1 indoor unit and 1 outdoor unit)
(Indoor unit)
Distributor
(Strainer incorporated)
TC sensor
Liquid side
(Outer dia : ØB)
To outdoor unit
Dimension table
Outer diameter of refrigerant pipe
Indoor unit
SM56 type
SM80, 110, 140, 160
type
• Twin type (Combination of 2 indoor units and 1 outdoor unit)
(Indoor unit A)
Distributor
(Strainer incorporated)
TC sensor
Liquid side
(Outer dia : ØA)
Branch pipe
Liquid side
(Outer dia : ØC)
To outdoor unit
Indoor unit
Branch pipe
RBC-TWP30E2
SM56 × 2
SM80 × 2
RBC-TWP50E2
TCJ sensor
Strainer
Heat
exchanger
Gas side
(Outer dia : ØA)
To outdoor unit
Gas side ØA
Liquid side ØB
12.7
6.4
15.9
9.5
TCJ sensor
Strainer
Heat
exchanger
Gas side
(Outer dia : ØB)
A
6.4
9.5
Heating
Cooling
Capillary tube specifications
Model
RAV-SM∗∗∗CTP∗
SM56 type
SM80 type
SM110, 140 , 160
type
Distributor
(Strainer incorporated)
TC sensor
Liquid side
(Outer dia : ØA)
Branch pipe
B
C
D
12.7
9.5
15.9
15.9
9.5
15.9
– 18 –
FILE NO. SVM-13050
Inner dia. × Length × Q'ty
Ø2 × 300 × 1, Ø2 × 350 × 1
Ø2 × 800 × 1
Ø2 ×
300
× 1, Ø2 × 350 × 2
Ø2 × 400 × 1
Ø2 × 150 × 1, Ø2 × 200 × 2
Ø2 × 250 × 1, Ø2 × 300 × 1
Ø2 × 350 × 1, Ø2 × 1000 × 1
(Indoor unit B)
TCJ sensor
Strainer
Heat
exchanger
Gas side
(Outer dia : ØB)
Liquid side
(Outer dia : ØD)
To outdoor unit
Heating
Cooling

Advertisement

Table of Contents
loading

Table of Contents