Split type indoor unit ceiling type
Hide thumbs Also See for RAV-SM567CTP-E (TR):
Table of Contents

Advertisement

No.
Item
22
8°C heating/
1) This functional is intended for the cold latitudes and performs
Frost protective
operation
2) This function is valid only for combination with the outdoor
3) Using the indoor DN code [D1] (1 bit), Valid/Invalid of this
4) This operation is the heating operation which sets 8°C as
5) This function starts operation by pushing temperature
6) To stop/release this operation, select and execute one from
7) As the setup temperature is 8°C and the human heating is not
8) The settings of the air direction and air volume are
9) The indoor fan stops to protect the compressor for
Outline of specifications
objective heating operation (8°C heating operation).
units (Super Digital Inverter (SDI) 4-series outdoor units).
function is set up at the customer's side.
∗ The setup by DN code is Invalid [0]/Valid [1] and Invalid [0]
has been set at the shipment.
the setup temperature of the target.
button
during heating operation; besides by pushing
button for 4 seconds or more after temperature
reached the minimum set temperature.
the following operations.
Push
button: Heating operation (18°C setting)
continues.
Push [START/STOP] button: Air conditioner stops.
(Heating 18°C operation at the next start)
MODE
Push
: Other operation mode is selected and the
operation continues.
targeted, the cold air discharge preventive control (Item 7) is
made invalid to suppress the intermittent operation.
changeable during this operation.
2 minutes after start of heating operation (Thermo-ON) by
this function.
– 36 –
FILE NO. SVM-13050
Remarks
In a group connection,
if there is even one
combination with other
unit, "This function is not
provided." is displayed.
The setup temperature
jumps from [18] to [8].