Information As Per En 54-4, Chapter - Bosch FPC-500-2 Installation Manual

Conventional fire panel
Hide thumbs Also See for FPC-500-2:
Table of Contents

Advertisement

Conventional Fire Panel
6.4
Information as per EN 54‑4, chapter 7.1
a) This is a power supply unit that is installed in the FPC‑500
Fire Panel. It provides power to the device and the connected
peripherals and is used to charge the two connectable batteries.
b) Technical data
1) Recommended power
output
2) Power supply
Operating voltage
3) Communication
parameters
4) Fuse values
5) Batteries
6) Max. current
consumption
7) Max. battery inner
resistance
8) I
I
max, a
I
max, b
9) Cable parameters
Battery
Board power supply
230-V power supply
Bosch Sicherheitssysteme GmbH
min
Technical Data | en
61 W
230 VAC +10%/-15%, 50–60 Hz
26 VDC to 29 VDC
None
3.15 A/250 V
2 x 7.0–7.2 Ah (max.) lead gel
battery
2.3 A
800 mOhm
70 mA
0.7 A
2.3 A
Cable enclosed
Wired ex works
1.5-mm
standard cable
2
2014.06 | 7.0 | F.01U.172.980