Fire Alarm Systems | FPA‑1000 Analog Addressable Fire Panels
FPA‑1000 Analog Addressable Fire Panels
www.boschsecurity.com
The FPA‑1000 Analog Addressable Fire Panels are a
scalable solution for fire detection. Protect your small
office with a single system or connect multiple panels
together as your needs grow. Networking capabilities
support the monitoring of up to 8 interconnected
panels (2,000 addressable points) in one system for
campuses or other large commercial environments.
The FPA‑1000 panels combine complete built-in Fire
Alarm Control Panel (FACP) equipment such as
Notification Appliance Circuits (NACs), Signaling Line
Circuits (SLCs), relays, power supply, Digital Alarm
Communicator Transmitter (DACT), and Ethernet
connection with expandability using the option bus or
plug‑in boards. The two integrated NACs can be
expanded with remote addressable NAC power
boosters and programmed with specific activation
patterns.
The control panel includes one SLC that supports 254
addressable points (254 analog detectors or modules,
or 127 analog sounder bases in combination with a
suitable detector). The control panel is easily
expandable with the FPE‑1000‑SLC Signaling Line
Circuit Plug-in Module, doubling the address points to
508.
Support for up to 508 points on two analog
u
addressable loops
Built-in Ethernet connector for web-browser based
u
programming and Conettix Alarm-over-IP
communication
Two on-board NACs and dual-line PSTN DACT
u
Peer-to-peer networking of up to eight -V2 panels in
u
a single group
Suited to a wide range of applications and
u
compatible with the latest Bosch solutions -
including 440 Series Multi-criteria detectors
The panel has a compact and solid metal housing with
a keyed lock and a removable dead front door to
access electronics. It features surface and semi-flush
mounting options. On the front of the panel, six light-
emitting diodes (LEDs) show Fire, Carbon Monoxide
(Gas) Alarm, Power, Supervisory, Silenced, and
Trouble conditions. The built‑in keypad can be used
for total system control and programming even when
wearing fireman gloves. In addition, a large 4‑line by
20‑character alphanumeric LCD display shows
programmed device point information. Four keys
enable Drill, Reset, Silence, and Acknowledge
functions.
The FPA‑1000 panels enable various programming
approaches:
• Front panel programming
• On-site programming, using a laptop with the
possibility of pre-programming at the office
• Off-site programming, with remote access via
Ethernet (browser-based)
Front panel programming provides an auto‑learn
function, allowing the installer to configure the system
quickly and easily in default mode. Using a local laptop
or remote access communication, the programming is
carried out by means of a browser‑based user

Advertisement

loading

Summary of Contents for Bosch FPA‑1000 Series

  • Page 1 Peer-to-peer networking of up to eight -V2 panels in a single group Suited to a wide range of applications and compatible with the latest Bosch solutions - including 440 Series Multi-criteria detectors The FPA‑1000 Analog Addressable Fire Panels are a The panel has a compact and solid metal housing with scalable solution for fire detection.
  • Page 2 2 | FPA‑1000 Analog Addressable Fire Panels interface. Therefore, no software installation is miscellaneous reporting functions such as dialing required. The panel can receive diagnostics from a control and transmission supervision, priorities of Web browser running on an internet‑connected PC. report groups, routing to destinations, manual and auto test reports, and Anti-Replay feature.
  • Page 3: Installation/Configuration Notes

    Control Units, System (ANSI/UL 864) zones each • eight D7030X Series/D7032 combinations FPA-1000 • two Octal Relay Modules or Octal Driver Modules CSFM see the Bosch website (www.boschse- • four FPP‑RNAC‑8A‑4C Remote Notification Appliance curity.com) Circuit Power Supplies FDNY- 6101...
  • Page 4 4 | FPA‑1000 Analog Addressable Fire Panels Detectors connected to a sounder base can use only Auxiliary power supply addresses 1 to 127. The sounder bases are addressed AUX/FWR Full Wave Rectified 500 mA at 24 V FWR (17 to automatically by the panel, depending on the 31 VRMS), non‑switched, power- detector’s address (detector address +127).
  • Page 5: Ordering Information

    5 | FPA‑1000 Analog Addressable Fire Panels Accessories City Tie BATB-40 Battery box/enclosure, 22x20.75x7.25" City Tie - Local Energy Mode Holds two dry or wet cell batteries. Optional BATB- SHELF battery shelf increases number of batteries. Type of connection In series Suitable for residential/commercial fire or burglary Alarm, trip coil 24 VDC...
  • Page 6 6 | FPA‑1000 Analog Addressable Fire Panels FAA-325-B4 Analog sensor base, 4" FAD-325-V2F-R Kit, analog duct housing w/relays & head Is combined with analog addressable detectors that Duct detector housing with an FAD-325-V2F-DH Analog use the advanced digital communication protocol to duct smoke head and two sets of Form C alarm relays.
  • Page 7 7 | FPA‑1000 Analog Addressable Fire Panels FLM-325-2R4-2A Dual relay module, 2A FLM-325-NA4 Supervised output module, Class A/B Provides 2 A current at two independently-controlled Can be wired for Class A or Class B circuits, Form C contacts for a variety of Normally Open and compatible with 254 addresses Normally Closed applications, compatible with 254 Order number...
  • Page 8: Order Number

    Phone: +1 800 289 0096 Phone: +65 6571 2808 emea.securitysystems@bosch.com www.boschsecurity.com Fax: +1 585 223 9180 Fax: +65 6571 2699 emea.boschsecurity.com onlinehelp@us.bosch.com apr.securitysystems@bosch.com www.boschsecurity.us www.boschsecurity.asia © Bosch Security Systems 2017 | Data subject to change without notice 2690096139 | en, V14, 25. Oct 2017...

This manual is also suitable for:

Fpa-1000-v2Fpa-1000-lcFpa-1000-lt