Screed Program - Viessmann Vitocal 300-G Installation And Service Instructions Manual

Compact heat pump with electric drive type bw/bwc, ww/wwc
Table of Contents

Advertisement

Heat pump for drying buildings
Parameter
7300
This setting determines whether the
heat pump is used to dry the building
as well as the instantaneous heating
water heater.
Access
"Device settings"
"Programming"
"Internal hydraulics"

Screed program

Parameter
7303
!
Please note
Risk of damage to building
through overheating screed at
high flow temperatures.
Prevent high flow temperatures
through a temperature limiter
as maximum limiter for under-
floor heating systems.
Note
Observe the specifications of
EN 1264-4. The report to be provided
by the heating contractor must con-
tain the following heat-up details:
Heat-up data with respective flow
temperatures
Max. flow temperature achieved
Operating condition and outside
temperature during handover
Control settings, hydraulics
This function must be set to "NO" if
the heat pump is not ready for opera-
tion because the heat pump primary
circuit is not ready when building dry-
ing takes place.
y to "HP for dry. building"
"YES" or "NO"
Standard setting
Setting range
The function continues after a
power failure or after the control unit
has been switched OFF.
The selected operating program
continues, if the "Screed program"
has terminated in accordance with
the program or, before its expiry, the
temperature/time profile "0" is
selected.
The temperature/time profiles 7 to
12 regulate to the maximum flow
temperature.
The screed program affects all
enabled heating circuits in parallel.
The set temperature is limited by
parameter "Max. flow temp." for the
heating circuit, even if the time pro-
file has been selected with a higher
set flow temperature.
No
Yes/No
159