Viessmann Vitocal 300-G Installation And Service Instructions Manual page 124

Compact heat pump with electric drive type bw/bwc, ww/wwc
Table of Contents

Advertisement

Troubleshooting
Control unit diagnostics
ID
Message
(priority)
6B
Ext. Heat
source ("U")
70
Room tem-
perature sen-
sor HK1 ("U")
71
Room tem-
perature sen-
sor HK2 ("U")
72
Room tem-
perature sen-
sor HK3 ("U")
73
Room tem-
perature sen-
sor NC ("U")
78
Room tem-
perature sen-
sor HK1 ("U")
79
Room tem-
perature sen-
sor HK2 ("U")
7A
Room tem-
perature sen-
sor HK3 ("U")
124
(cont.)
1.
Cause
2.
Measures
1.
Break, external heat source tem-
perature sensor
2.
Check the sensor and replace, if
required
1.
Short circuit, room temperature sen-
sor, heating circuit 1
2.
Check the sensor and replace, if
required
(see Vitotrol installation instructions)
1.
Short circuit, room temperature sen-
sor, heating circuit 2
2.
Check the sensor and replace, if
required
(see Vitotrol installation instructions)
1.
Short circuit, room temperature sen-
sor, heating circuit 3
2.
Check the sensor and replace, if
required
(see Vitotrol installation instructions)
1.
Short circuit, room temperature sen-
sor NC
2.
Check the sensor and replace, if
required
1.
Break, room temperature sensor,
heating circuit 1
2.
Check the sensor and replace, if
required
(see Vitotrol installation instructions)
1.
Break, room temperature sensor,
heating circuit 2
2.
Check the sensor and replace, if
required
(see Vitotrol installation instructions)
1.
Break, room temperature sensor,
heating circuit 3
2.
Check the sensor and replace, if
required
(see Vitotrol installation instructions)
Access
right
Customer
Customer
Customer
Customer
Customer
Customer
Customer
Customer

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents