Troubleshooting
Control unit diagnostics
ID
Message
(priority)
D4
Control high
pressure ("i")
D6
Flow switch
("U")
E1
Ext. Heat gen-
eration ("U")
E2
Fault, lag heat
pump ("U")
FF
New start ("i")
Heat pump characteristics in case of messages
All messages have a 2-digit number as identifier, the so-called "ID". This num-
ber corresponds to the ID in the table above "Message display" from page 120.
ID
Characteristics and effects of system/control unit
10
Outside temperature is assumed to be -40 °C.
18
20
The temperature value of the secondary return sensor plus 5 K is se-
28
lected. The heat pump is stopped (message A9) if the secondary flow
and return temperature sensors are faulty.
21
The temperature value of the secondary flow sensor plus 5 K is se-
29
lected. The heat pump is stopped (message A9) if the secondary flow
and return temperature sensors are faulty.
130
(cont.)
1.
Cause
2.
Measures
1.
Air in the heating circuit; secondary
or heating circuit pump blocked; con-
denser contaminated; pressure sen-
sor faulty
2.
Vent heating circuit; check second-
ary and heating circuit pump; flush
heating circuit; check system pres-
sure
1.
The flow switch has responded;
inadequate throughput
2.
Check primary pumps and circula-
tion pump for brine/primary circuit.
For type WW/WWC check filter and
intermediate circuit heat exchanger;
check primary circuit pressure
1.
Fault on the external heat source
2.
Check external heat source
1.
Fault at the lag heat pump in a cas-
cade
2.
Check the lag heat pump display
1.
Control unit restart
2.
No measures required
Access
right
Contractor
Customer
Customer
Customer
Customer