9-14. Table of Self-Diagnostic Functions and Corrections
Cause
Wired remote
controller
Indoor unit
display
receiver lamp
1:1 connection (Single type)
(Field supply)
Nothing is
Nothing is
• Indoor operation switch is OFF.
displayed
displayed
• Indoor unit power is not ON.
• Automatic address setting has not been
completed.
E01 displayed
• Inter-unit control wiring is cut or is not
connected correctly.
Operating lamp
is blinking.
E14 displayed
——————
• Indoor-outdoor inter-unit wiring is not
E04 displayed
connected correctly.
E06 displayed
——————
Standby lamp is
blinking.
• Indoor unit capacity is too low.
E15 displayed
• Indoor unit capacity is too high.
E16 displayed
Operation lamp
• Reversed phase in the outdoor unit
and Standby
single-phase or open phase in the
P05 displayed
lamp are blinking
outdoor unit 3-phase power.
alternately.
L02 displayed
• Indoor-outdoor unit type mismatch.
• Indoor-outdoor units are not setting
L13 displayed
correctly.
Both the
Operation lamp
L04 displayed
——————
and Standby
lamp are blinking
together.
L07 displayed
——————
Operation lamp
• No gas
and Standby
P15 displayed
lamp are blinking
alternately.
Group connection
Correction
(Simultaneous multi
system)
• Same at left.
• Set the indoor operation switch ON.
• Turn ON the indoor unit power.
• Same at left.
• Check the inter-unit control wiring.
• Perform automatic address setting
(See 9-15).
• Remote controller
• Check the remote controller crossover
crossover wiring is cut
wiring.
or is not connected
• Perform automatic address setting again.
correctly.
• Same at left.
• Connect the wiring correctly.
• Inter-unit control
• Refer to 9-15 System Control, and make
wiring is cut or is not
the correct settings.
connected correctly.
• Same at left.
• Check that the total capacities of the indoor
and outdoor units are appropriate.
• Same at left.
• Reverse 2 phases of the outdoor unit
3-phase power and connect them correctly.
• Same at left.
• Connect the units correctly.
• Same at left.
• Connect the units correctly.
• Same at left.
• Connect the units correctly.
• Outdoor unit address is
• Connect the units correctly.
duplicated.
• Remote controller
• Perform automatic address setting
crossover wiring is
(See 9-15).
connected to the indoor
unit, however, it is set
for individual operation.
• Same at left.
• Check the refrigerant cycle (for gas leaks).
29
9-15. System Control
System control refers to the link wiring connection for control of
simultaneous-operation multi systems, group control, and main-
sub remote controller control.
9-15-1. Basic wiring diagram 1
Single type
● Be careful to avoid miswiring when connecting the wires.
(Miswiring will damage the units.)
(for 3-phase outdoor unit)
Example: Using a wireless remote controller with a system
Ground
System address (S2)
(Setting at shipment: "0")
Leakage breaker
Outdoor unit
L1
L2
L3
N
1 2
(Using a wired remote controller with a
single-type system)
Inter-unit control wiring
1. To connect the remote controller, a
remote controller cord is required.
Leakage breaker
L
N
Indoor
1
Leakage breaker
Leakage breaker
unit
2
No. 1
4P
terminal
Ground
L1
plate
Ground
L2
L
2P
Out-
L3
N
(white)
Indoor
1
door
N
unit
2
Wireless remote
unit
1
controller
2
Wired remote
controller
Ground
(Field
supply)
1 2
white black
Fig. 9-10
(Wiring procedure)
(1) Connect the crossover wiring to 1 and 2 on the remote
controller wiring terminal plate for units.
(2) Connect the inter-unit control wiring to 1 and 2 on the No.
1 indoor unit terminal plate, and to 1 and 2 on the outdoor
unit terminal plate.
Also connect the inter-unit control wiring between the
indoor units.
(3) When the indoor and outdoor unit power is turned ON,
automatic address setting is performed (when there is only
1 outdoor unit or when the system address is "0").
NOTE
* If the system address is "0", automatic address setting is
performed when the power is turned ON (in the case shown in
Basic wiring diagram 1).
This requires approximately 4 – 5 minutes (when the outdoor /
indoor unit ratio is 1:1 as shown in Basic wiring diagram 1).
During automatic address setting, LED 1 and 2 on the outdoor
unit control PCB blink alternately. These LED turn OFF when
automatic address setting is completed.