Panasonic EAIRC-MJ Series Installation Instructions Manual

Vrf system air conditioner for refrigerant r410a, for indoor/outdoor units

Advertisement

Quick Links

INSTALLATION INSTRUCTIONS
For Indoor Units EAIRC-MJ, EAIRC-MS Types
■ R410A Models
Model No.
Indoor Units
Indoor Unit Type
EAIRC-MJ
Jetflow Air Curtain
EAIRC-MS
Standard Air Curtain PAW-10EAIRC-MS¹
1 Requires 1 Solenoid Valve Kit CZ-P160HR3 when combined with 3-pipe systems.
2 Requires 2 RAP Valve Kits CZ-160RVK2 when combined with 2-pipe multi-systems.
Requires 2 Solenoid Valve Kits CZ-P160HR3 when combined with 3-pipe systems.
Outdoor Units
MF2
3-PIPE
ME1
2-PIPE
2-PIPE
LE1
GF2
3-PIPE
GE2
2-PIPE
2-PIPE,
GEP2
High Power
* Refrigerant R410A is used in the outdoor units.
IMPORTANT NOTICE!
Please read before starting
Preparation for operation
Before operating the Air Curtain unit, it is absolutely mandatory to carefully read
and to strictly execute the instructions and settings in Chapter 8.
Failure to follow instructions
The manufacturer shall in no way be responsible for improper installation,
problems in operation, malfunction of the unit or safety hazards resulting from
failure to follow the instructions in this manual.
– VRF System Air Conditioner –
for Refrigerant R410A
4
PAW-10EAIRC-MJ¹ PAW-15EAIRC-MJ² PAW-20EAIRC-MJ² PAW-25EAIRC-MJ²
U-8MF2E8, U-10MF2E8, U-12MF2E8, U-14MF2E8, U-16MF2E8
U-8ME1E81, U-10ME1E81, U-12ME1E81, U-14ME1E81, U-16ME1E81, U-18ME1E81,
U-20ME1E81
U-4LE1E5, U-4LE1E8, U-5LE1E5, U-5LE1E8, U-6LE1E5, U-6LE1E8
U-16GF2E5, U-20GF2E5, U-25GF2E5
U-16GE2E5, U-20GE2E5, U-25GE2E5, U-30GE2E5
U-16GEP2E5, U-20GEP2E5, U-25GEP2E5
8
10
PAW-20EAIRC-MS²
14

Advertisement

Table of Contents
loading

Summary of Contents for Panasonic EAIRC-MJ Series

  • Page 1 INSTALLATION INSTRUCTIONS – VRF System Air Conditioner – for Refrigerant R410A For Indoor Units EAIRC-MJ, EAIRC-MS Types ■ R410A Models Model No. Indoor Units Indoor Unit Type EAIRC-MJ Jetflow Air Curtain PAW-10EAIRC-MJ¹ PAW-15EAIRC-MJ² PAW-20EAIRC-MJ² PAW-25EAIRC-MJ² EAIRC-MS Standard Air Curtain PAW-10EAIRC-MS¹ PAW-20EAIRC-MS² 1 Requires 1 Solenoid Valve Kit CZ-P160HR3 when combined with 3-pipe systems.
  • Page 2: Important

    IMPORTANT! Please Read Before Starting • To prevent possible hazards from insulation failure, This air conditioning system meets strict safety and the unit must be grounded. operating standards. As the installer or service person, it is an important part of your job to install or service the When Transporting system so it operates safely and efficiently.
  • Page 3 When Servicing • Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring. • Keep your fingers and clothing away from any moving parts. • Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
  • Page 4: Check Of Density Limit

    Check of Density Limit The standards for minimum room volume are as follows. (1) No partition (shaded portion) The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its density will not exceed a set limit. The refrigerant (R410A), which is used in the air conditioner, is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws imposed to protect the ozone layer.
  • Page 5: Table Of Contents

    CONTENTS Page 7. HOW TO INSTALL WIRELESS REMOTE IMPORTANT ........2 CONTROLLER RECEIVER .
  • Page 6: General

    1. GENERAL 2. SELECTING THE INSTALLATION SITE This booklet briefly outlines where and how to install the 2-1. Indoor Unit air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all AVOID: accessory parts listed are with the system before beginning.
  • Page 7: How To Install The Indoor Unit

    3. HOW TO INSTALL THE INDOOR UNIT ■ Air Curtain (EAIRC-MJ, EAIRC-MS Types) 3-1. Dimensions and Required Minimum Space for Installation and Service (EAIRC-MJ Type) This air conditioner (air curtain) is usually installed freely ● suspended from the ceiling. ● The ceiling must be strong enough to support the weight of the unit.
  • Page 8: Dimensions And Required Minimum Space For Installation And Service (Eairc-Ms Type)

    3-2. Dimensions and Required Minimum Space for Installation and Service (EAIRC-MS Type) This air conditioner (air curtain) is usually installed freely ● suspended from the ceiling. ● The ceiling must be strong enough to support the weight of the unit. ●...
  • Page 9: Suspending The Indoor Unit

    3-3. Suspending the Indoor Unit (4) Use the existing fixing points on the top side of the unit. The number of fixing points depends on the length of the Depending on the ceiling type: air curtain. Insert suspension bolts as shown in Fig. 3-3 ●...
  • Page 10: Solenoid Valve Kit For 3-Pipe Ecoi Systems (Cz-P160Hr3)

    ■ Solenoid Valve Kit for 3-pipe ECOi systems the subsection “How to use the fittings” in the section “Valve Dimensions and Hanging Method.”) (CZ-P160HR3) for R410A When installing the valve body, install it with the top surface ● 3-5. Installing the Solenoid Valve Kit (SVK) facing up.
  • Page 11 9P connector Liquid tube ID: 9.52 mm Liquid tube ID: 9.52 mm Cabtyre cable (5 m) Suction tube ID: 15.88 mm Hanging hook Suction tube ID: 15.88 mm Front side Discharge tube ID: 12.7 mm Service cover Unit: mm Fig. 3-11 Note: This figure shows the unit with suspension fittings attached.
  • Page 12 4. Wiring, Tubing and Heat Insulation Refrigerant Tubing When brazing, be sure to perform nitrogen replacement inside the tube so that oxidation coating does not form inside the tube. ● Cool with damp cloth or other means when brazing the jont with a torch. Otherwise, the solenoid valve will be damaged.
  • Page 13: Installing The Refrigerant Tubing

    4. ELECTRICAL WIRING Heat insulation (Be sure to insulate the tubing after finishing leak inspection.) 4-1. General Precautions on Wiring Be sure to insulate the tubing. ● (1) Before wiring, confirm the rated voltage of the unit as Wrap insulators (field supply) having a thickness of 10 mm ●...
  • Page 14: Wiring System Diagrams

    4-3. Wiring System Diagrams Example: EAIRC-MJ Type Indoor unit (No. 1) Power supply Outdoor unit 220 – 240V ~50/60Hz INV unit Ground Power supply Remote 380 – 415V, 3 N~, 50Hz controller Ground Ground Ground Indoor unit Ground (No. 2) Inter-outdoor-unit control wiring Power supply Ground...
  • Page 15 CAUTION (1) When linking the outdoor units in a network, disconnect the terminal extended from the short plug from all outdoor units except any one of the outdoor units. (When shipping: In shorted condition.) For a system without link (no wiring connection between outdoor units), do not remove the short plug. (2) Do not install the inter-unit control wiring in a way that forms a loop.
  • Page 16 How to connect wiring to the terminal ■ For stranded wiring (1) Cut the wire end with cutting pliers, Stranded wire Special Screw then strip the insulation to expose washer the stranded wiring about 10 mm and Ring pressure tightly twist the wire ends. (Fig. 4-8) Ring pressure terminal Screw and...
  • Page 17 ■ Electric Diagram for PAW-20EAIRC-MS and PAW-15/20/25EAIRC-MJ Fig. 4-15 shows the electric diagram for the PAW-20EAIRC-MS and PAW-15/20/25EAIRC-MJ models. Fig. 4-15...
  • Page 18: How To Process Tubing

    5. HOW TO PROCESS TUBING Caution Before Connecting Tubes Tightly (1) Apply a sealing cap or water-proof tape to prevent dust or The liquid tubing side is connected by a flare nut, and the gas water from entering the tubes before they are used. tubing side is connected by brazing.
  • Page 19: Insulating The Refrigerant Tubing

    For the flare nuts at tubing connections, be sure to use the Flare insulator (supplied) ● flare nuts that were supplied with the unit, or else flare nuts Insulation tape (white) Flare union for R410A (type 2). The refrigerant tubing that is used must (supplied) be of the correct wall thickness as shown in the table below.
  • Page 20: Finishing The Installation

    7. HOW TO INSTALL WIRELESS 5-5. Finishing the Installation REMOTE CONTROLLER RECEIVER After finishing insulating and taping over the tubing, use sealing putty to seal off the hole in the wall to prevent rain and draft from entering. (Fig. 5-10) NOTE Apply putty here Refer to the Operating Instructions attached to the optional Wire-...
  • Page 21 2. Then go to setting mode 2. 1. After finishing the addressing procedure (refer to the outdoor unit test run service manual supplied with the Setting mode 2 outdoor unit), note down the address of the air curtain unit such as 1-1 or 2-18 etc. and go to the outdoor unit electrical board.
  • Page 22 9. APPENDIX Care: After a prolonged idle period Check the indoor and outdoor unit air intakes and outlets for ■ Care and Cleaning blockage; if there is a blockage, remove it. Care: Before a prolonged idle period WARNING Operate the fan for half a day to dry out the inside. ●...
  • Page 23 ■ Troubleshooting If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work properly, contact your dealer or a service center. Indoor unit ● Symptom Cause Noise Sound like streaming water during Sound of refrigerant liquid flowing inside unit ●...
  • Page 24 Check Before Requiring Services ● Symptom Cause Remedy Air conditioner does not run Power failure or after power failure Press ON/OFF operation button on remote control at all although power is turned unit again. Operation button is turned off. Switch on power if circuit breaker is turned off. ●...
  • Page 25 ■ Technical Data ● EAIRC-MJ Types Air Curtain PAW-10EAIRC-MJ PAW-15EAIRC-MJ PAW-20EAIRC-MJ PAW-25EAIRC-MJ Air flow type Jetflow Air volume (high) m³/h 1800 2700 3600 4500 Air volume (medium) m³/h 1500 2300 3000 3800 Air volume (low) m³/h 1200 1900 2500 3100 Air flow length (A) Heating capacity (nominal) 11.4...
  • Page 26 ● EAIRC-MS Types Air Curtain PAW-10EAIRC-MS PAW-20EAIRC-MS Air flow type Standard Air volume (high) m³/h 1800 2700 Air volume (medium) m³/h 1500 2300 Air volume (low) m³/h 1200 1900 Air flow length (A) Heating capacity (nominal) 11.4 31.5 Cooling capacity (nominal) 17.5 Heating capacity with air in 20 °C, air out 40 °C...