Fault codes

Dis-
Const.
played
fault
code
10
X
18
X
19
X
Weath.-
System char-
comp.
acteristics
X
Regulates, as if
the outside
temperature
were 0 °C
X
Regulates, as if
the outside
temperature
were 0 °C
X
Regulates, as if
the outside
temperature
were 0 °C
Troubleshooting
Cause
Measures
Short circuit,
Check outside tem-
outside tem-
perature sensor
perature sen-
(see page 135)
sor
Lead break,
Check outside tem-
outside tem-
perature sensor
perature sen-
(see page 135)
sor
Communica-
Check wireless
tion interrup-
connection:
tion, outside
place outside tem-
temperature
perature sensor RF
sensor RF:
and wireless re-
outside tem-
peater close to the
perature sen-
boiler.
sor RF, KM
Check KM BUS to
BUS to wire-
wireless base sta-
less base sta-
tion.
tion, wireless
Log off outside
base station
temperature sen-
or wireless re-
sor and wireless
peater faulty
repeater, then log
or defective
them on again.
Replace outside
temperature sen-
sor RF.
Replace wireless
repeater.
Replace wireless
base station.
Wireless
base sta-
tion
117