Venting The Boiler By Flushing - Viessmann Vitodens 200-W Installation Instructions Manual

45 and 60 kw wall mounted gas condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Further details regarding the individual steps

Venting the boiler by flushing

B
32
1. Check the pre-charge pressure of the
diaphragm expansion vessel.
2. Close the gas shut-off valve.
3. Fill the heating system via boiler drain
& fill valve A. System pressure
> 1.0 bar (0.1 MPa).
4. Close boiler drain & fill valve A.
A
1. Close the shut-off valves on the heat-
ing water side.
2. Connect the drain hose to boiler drain
& fill valve B.
3. Open valves A and B. Vent under
mains pressure until no more air
noise can be heard.
4. Close taps A and B; open the shut-
A
off valves on the heating water side.
(cont.)