Further details regarding the individual steps
Remove residues of the leak detection
agent after testing.

Checking combustion quality

The electronic combustion controller
automatically ensures optimum combus-
tion quality. During commissioning/
maintenance, only the combustion val-
ues need to be checked. For this, meas-
ure the CO content plus the CO
content. For a description of the elec-
tronic combustion controller functions,
see page 160.
Note
To prevent operating faults and damage,
operate the appliance with uncontami-
nated combustion air.
CO content
■ The CO content must be < 1000 ppm
for all gas types.
CO
or O
content
2
2
■ The CO
content must be within the
2
following limits for upper and lower
heating output respectively:
– 7.5 to 9.5 % for natural gas E and LL
– 8.8 to 11.1 % for LPG P
■ For all gas types, the O
be between 4.0 and 7.6 %.
If the actual CO
or O
2
their respective ranges, check the bal-
anced flue system for tightness, see
page 41.
or O
2
2
content must
2
values lie outside
2
Commissioning, inspection, maintenance
(cont.)
Note
During commissioning, the combustion
controller carries out an automatic cali-
bration. Only measure the emissions
approx. 30 s after the burner has star-
ted.
A
1. Connect a flue gas analyser at flue
gas port A on the boiler flue con-
nection.
2. Open the gas shut-off valve, start the
boiler and create a heat demand.
3. Set the lower heating output (see
page 50).
4. Check the CO
2
actual value deviate from the afore-
mentioned ranges by more than 1 %,
implement steps on page 49.
5. Enter the actual values into the
report.
content. Should the