3.2 GENERATOR

SYMPTOM
No voltage
Low voltage
(below 100 Volts)
Very low voltage
(4-10 Volts AC)
3-6
Each symptom is followed by a probable cause and suggested solution. To isolate the
possible cause, proceed in a systematic manner to determine the faulty component. This
guide does not cover all possible situations that may occur under all conditions of operation.
PROBABLE CAUSE
• 35 Amp Breaker tripped
• Generator Belt loose/broken
• Generator belt loose/broken
• Engine air filter dirty
• Engine fuel system problem
• Engine exhaust system problem
• Engine speed low
• Wiring to capacitor
• Capacitor defective
Disconnect the batteries from the
APU before performing any repairs.
SOLUTION
• Determine reason and reset
• Tighten/replace
• Tighten/replace
• Clean/replace filter
• Change fuel filters
• Clean/replace
• Adjust
• Repair/replace
• Test and replace
62-11175 COMFORTPRO SERVICE MANUAL
WARNING
REFERENCE
• A-5
• A-2
• A-2
• A-3
• A-3
• 3- 13
• 3- 13, 3- 14