Minimum Clearances To Combustibles - Quadra-Fire 4100I-GD-B Manual

Wood insert advanced combustion technology (act)
Hide thumbs Also See for 4100I-GD-B:
Table of Contents

Advertisement

In Canada a full length six inch (152mm) S635 fl ue liner
required as per ULC S628.
March 27, 2008
4100-I ACT WOOD INSERT
CLEARANCES TO COMBUSTIBLES
United States and Canada
Maximum Mantel Depth - 10" (254mm)
A
F
Hearth Extension
Omni Report #061-S-40-2
A
Sidewall to Stove
B
Mantel to Stove
C
Top Trim to Stove
D
Side Trim to Stove
E
Hearth Extension from Glass
F
Hearth Extension from Side of Insert
Thermal Protection USA & Canada
Thermal protection must be 1/2 Inch (12.7mm) minimum
thickness ('k" value = 0.84) or equivalent material*
*Zero Clearance Installations USA Only
See Alternative Floor Protection Worksheet on page 7.
*
Mantel
B
Fascia or Trim
C
D
Insert
E
USA
15" (381mm)
26" (660mm)
20" (508mm)
6" (152mm)
16" (406mm)
8" (203mm)
NOTE: When installing into a masonry fi replace, the fi re-
place must be built to UBC Chapter 37 standards. Do not
remove brick or mortar from masonry fi replace to accom-
modate insert. The permanent metal warning plate provided
must be attached to the back of the fi replace stating the fi re-
place may have been altered to accommodate the insert and
must be returned to original condition for use as a conven-
tional fi replace.
250-7201 Rev D
CANADA
15" (381mm)
23" (584mm)
20" (508mm)
6" (152mm)
18" (457mm)
8" (203mm)
R
Page 5