Accessory parts

Q'ty
Part name
MAP080 MAP100 MAP120 MAP140
Owner's Manual
1
1
Installation Manual
1
1
CD-ROM
(Owner's manual,
1
1
Installation manual)
F-GAS label
1
1
Attached pipe
(Ø22.2 both forward
1
1
and downward)
Attached pipe
(Ø15.9 both forward
1
1
and downward)
Attached pipe
(Ø12.7 for draw-out
1
1
forward)
Attached pipe
(Ø12.7 for draw-out
1
1
downward)
Attached pipe
(Ø28.6 both forward
and downward)
Attached pipe
(Ø19.1 both forward
and downward)
Attached pipe
(Ø15.9 for draw-out
forward)
Attached pipe
(Ø15.9 for draw-out
downward)
Attached pipe
(Ø19.1 both forward
and downward)
Attached pipe
(Ø15.9 for draw-out
forward)
Attached pipe
(Ø15.9 for draw-out
downward)
9-EN
Shape
Usage
1
1
(Be sure to hand it to the customers.)
1
1
(Be sure to hand it to the customers.)
For other languages that do not appear in
1
1
this Installation Manual, Please refer to the
enclosed CD-ROM.
Fill the items on the label after adding
1
1
refrigerant.
Suction-side gas pipe
Ø25.4 → Ø22.2 pipe fitting
Discharge-side gas pipe
Ø15.9 → Ø19.1 pipe fitting
* Flare the connector on the outdoor unit for
installation
Liquid-side connection pipe
* Flare the connector on the outdoor unit for
installation
Suction-side gas pipe
1
1
Ø25.4 → Ø28.6 pipe fitting
Discharge-side connection pipe
1
* Flare the connector on the outdoor unit for
installation
1
Liquid-side gas pipe
Ø15.9 → Ø12.7 pipe fitting
*
Flare the connector on the outdoor unit for
1
installation
Discharge-side gas pipe
Ø19.1 → Ø22.2 pipe fitting
1
* Flare the connector on the outdoor unit for
installation
1
Liquid-side connection pipe
*
Flare the connector on the outdoor unit for
installation
1
– 5 –
3
Installation of new refrigerant air
conditioner
This air conditioner adopts the new HFC refrigerant (R410A) which does not deplete the ozone layer.
• R410A refrigerant is vulnerable to impurities such as water, oxidizing membranes, or oils because the pressure
of R410A refrigerant is higher than that of the former refrigerant by approximately 1.6 times.
As well as the adoption of the new refrigerant, the refrigerating oil has been also changed. Therefore, pay
attention so that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle of the
new refrigerant air conditioner during installation.
• To prevent mixing of refrigerant or refrigerating oil, the size of the charge port of the main unit or connecting
section of the installation tool differs to that of an air conditioner for the former refrigerant.
Accordingly, exclusive tools are required for the new refrigerant (R410A) as shown below.
• For connecting pipes, use new and clean piping materials so that water or dust does not enter.
 Required tools and cautions on handling
It is necessary to prepare the tools and parts for installation as described below. The tools and parts which will be
newly prepared in the following items should be restricted to exclusive use.
Explanation of symbols
: Newly prepared (It is necessary to use it exclusively with R410A, separately from those for R22 or R407C.)
: Former tool is available.
Used tools
Gauge manifold
Vacuuming, charging refrigerant
and operation check
Charging hose
Charging cylinder
Charging refrigerant
Gas leak detector
Checking gas leak
Vacuum pump
Vacuum drying
Vacuum pump with counterflow
Vacuum drying
Flare tool
Flare processing of pipes
Bender
Bending processing of pipes
Refrigerant recovery device
Recovering refrigerant
Torque wrench
Tightening flare nut
Pipe cutter
Cutting pipes
Refrigerant canister
Charging refrigerant
Welding machine / Nitrogen gas
Welding of pipes
cylinder
Refrigerant charging balance
Charging refrigerant
Usage
Proper use of tools / parts
Exclusive to R410A
Exclusive to R410A
Unusable (Use the Refrigerant charging balance.)
Exclusive to R410A
Usable if a counter-flow preventive adapter is
attached
R22 (Existing article)
Usable by adjusting size
R22 (Existing article)
Exclusive to R410A
Exclusive to Ø12.7 mm and Ø15.9 mm
R22 (Existing article)
Exclusive to R410A
Enter the refrigerate name for identification
R22 (Existing article)
R22 (Existing article)