◆ Address setting procedure 2
1
Set a system address for each system using SW 13 and 14 on the interface P.C. board on the
header outdoor unit of each system.
(Factory default: Address 1)
NOTE
Be sure to set a unique address on each system. Do not use a same address as another system (refrigerant line) or a custom
side.
Interface P.C. board on the header outdoor unit
SW06
SW07
SW09
1 2 3 4
1 2 3 4
1 2 3 4
SW11
SW12
SW13
1 2 3 4
1 2 3 4
1 2 3 4
Switch settings for a line (system) address on the interface P.C. board on the outdoor unit
(: switch ON, ✕: switch OFF)
SW13
Line (system) address
1
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
47-EN
SW10
1 2 3 4
SW14
1 2 3 4
SW14
3
4
1
2
3
Line (system) address
1
26
27
28
"–": not used for system address setting (Do not change their positions.)
2
Be sure to disconnect the relay connectors between the [U1U2] and [U3U4] terminals on all the
header outdoor units that will be connected to the central control. (Factory default: disconnected)
3
Turn on indoor units first, and then turn on outdoor units.
4
About 1 minute after turning the power on, confirm that the 7-segment display on the interface
4
P.C. board of the header outdoor unit indicates
5
Press SW 15 to start the automatic address setting.
(It may take up to 10 minutes (normally about 5 minutes) to complete one line's setting.)
6
The 7-segment display indicates
After the indication,
When the flashing stops and
complete.
7
4
6
Repeat steps
to
for other refrigerant lines.
8
After completing address setting of all systems, turn off dip switch 2 of SW30 on the interface P.C.
boards of all the header outdoor units connected to the same central control, except the unit that
has the lowest address.
(For unifying the termination of the wiring for the central control of indoor and outdoor units)
– 24 –
SW13
2
3
4
1
2
U1
U2
U3
U4
U5
U6
TO
TO
TO
CENTRAL
INDOOR
OUTDOOR
CONTROL
UNIT
UNIT
LER
U. 1. L08 (U. 1. flash)
Auto 1 → Auto 2 → Auto 3
.
U. 1. - - - (U. 1. flash)
starts flashing on the display.
U. 1. - - - (U. 1. light)
, remains lit on the display, the setting is
SW14
2
3
4
.
48-EN