Table 2
Model name of
Equivalent
outdoor unit
HP
MMY-
8 HP
MAP0804✽
10 HP
MAP1004✽
12 HP
MAP1204✽
14 HP
MAP1404✽
16 HP
AP1614✽
18 HP
AP1814✽
20 HP
AP2014✽
22 HP
AP2214✽
24 HP
AP2414✽
26 HP
AP2614✽
28 HP
AP2814✽
30 HP
AP3014✽
32 HP
AP3214✽
34 HP
AP3414✽
36 HP
AP3614✽
38 HP
AP3814✽
40 HP
AP4014✽
42 HP
AP4214✽
Charging of refrigerant
• Keeping the valve of the outdoor unit closed, be sure to charge the liquid refrigerant into the service port at the
liquid side.
• If the specified amount of refrigerant cannot be charged, fully open the valves of the outdoor unit at liquid and
gas sides, operate the air conditioner in COOL mode, and then charge refrigerant into service port at the gas
side. In this time, choke the refrigerant slightly by operating the valve of the canister to charge liquid refrigerant.
• The liquid refrigerant may be charged suddenly, therefore be sure to charge refrigerant gradually.
33-EN
Combination of outdoor unit
MMY-
Unit 1
Unit 2
Unit 3
MAP0804✽
MAP1004✽
MAP1204✽
MAP1404✽
MAP0804✽
MAP0804✽
MAP1004✽
MAP0804✽
MAP1004✽
MAP1004✽
MAP1204✽
MAP1004✽
MAP1404✽
MAP1004✽
MAP1404✽
MAP1204✽
MAP1404✽
MAP1404✽
MAP1004✽
MAP1004✽
MAP1004✽
MAP1204✽
MAP1004✽
MAP1004✽
MAP1404✽
MAP1004✽
MAP1004✽
MAP1204✽
MAP1204✽
MAP1204✽
MAP1404✽
MAP1204✽
MAP1204✽
MAP1404✽
MAP1404✽
MAP1204✽
MAP1404✽
MAP1404✽
MAP1404✽
– 17 –
 Full opening of the valve
Corrective of
Open the valves of the outdoor unit fully.
refrigerant
(kg)
2
Ø9.5 packed valve
Balance pipe
3
Using a 4 mm-hexagonal wrench, fully open the valve shaft.
8
Ø12.7 packed valve
10
Using a 4 mm-hexagonal wrench, fully open the
valve shaft.
0
1.5
Liquid side
3.5
7.5
8.5
11
12
Ø19.1 ball valve
2.5
Using a flathead screwdriver, turn it counterclockwise by 90° until it hits the stopper. (Full open)
5
6
8
Discharge gas
9.5
side
11
12.5
Ø25.4 ball valve
Using a wrench, turn the valve shaft counterclockwise by 90° until it hits the stopper. (Full open)
Suction gas side
After opening the valves fully, be sure to close the caps.
When you close the valve shaft, its cap and service port cap, see below chart.
Valve size
Ø9.5 packed valve
Ø12.7 packed valve
Ø15.9 packed valve
Ø19.1 ball valve
Ø25.4 ball valve
MAP080
MAP100
Ø15.9 packed valve
Using a 5 mm-hexagonal wrench, fully open the
valve shaft.
Valve
Service port
unit
Using flathead screwdriver, turn
it counterclockwise by 90° until
it hits the stopper. (Full open)
(1)
*
When opened fully, do not apply excessive torque
Flare nut
after the screwdriver hits the stopper; otherwise a
(2)
problem may be caused on the valve. (5 N•m or less)
Tightening torque
Valve shaft cap (N·m)
Service port cap (N·m)
14 to 18
14 to 18
20 to 25
14 to 18
33 to 42
14 to 18
20 to 25
14 to 18
20 to 25
14 to 18
MAP120
MAP140
Position of screwdriver slot
Fully opened
Fully closed
Slot
Fully opened
Fully closed
Valve shaft (N·m)
7 to 9
7 to 9
14 to 16
34-EN