Toshiba MMY-MAP0804FT8-E Installation Manual page 13

Air conditioner (multi type)
Hide thumbs Also See for MMY-MAP0804FT8-E:
Table of Contents

Advertisement

 Selection of pipe size
◆ Capacity code of indoor and outdoor units
Selection of pipe material
• For the indoor unit, the capacity code is decided at each capacity rank. (Table 1)
• The capacity codes of the outdoor units are decided at each capacity rank. The maximum number of connectable
indoor units and the total value of capacity codes of the indoor units are also decided. (Table 2)
Table 1
Capacity code
Indoor unit
Equivalent to
capacity rank
Equivalent to HP
007
0.8 HP
009
1 HP
012
1.25 HP
015
1.7 HP
018
2 HP
024
2.5 HP
027
3 HP
030
3.2 HP
036
4 HP
048
5 HP
056
6 HP
072
8 HP
096
10 HP
Table 2
Capacity code
Outdoor unit
Equivalent to
Equivalent to
model name
HP
capacity
MAP0804✽
8 HP
22.4
MAP1004✽
10 HP
28
MAP1204✽
12 HP
33.5
MAP1404✽
14 HP
40
AP1614✽
16 HP
45
AP1814✽
18 HP
50.4
AP2014✽
20 HP
56
AP2214✽
22 HP
61.5
AP2414✽
24 HP
68
AP2614✽
26 HP
73
AP2814✽
28 HP
78.5
AP3014✽
30 HP
85
AP3214✽
32 HP
90
AP3414✽
34 HP
96
AP3614✽
36 HP
101
AP3814✽
38 HP
106.5
AP4014✽
40 HP
112
AP4214✽
42 HP
118
* For combination of the outdoor units, refer to "Combination of outdoor units".
23-EN
Header
unit A
capacity
2.2
Outdoor
2.8
unit
3.6
4.5
(1)
5.6
Balance
pipes
7.1
Ø9.5
(1)
8
9
Liquid
pipe
11.2
14
16
Discharge-side
gas pipe
22.4
28
Suction-side
gas pipe
No. of
(2)
(9)
indoor
units
13
16
20
(3) Main piping
23
27
30
33
37
40
43
47
48
48
48
48
48
48
48
NOTE
Compared with the capacity code of the outdoor unit, the total value of capacity codes of the connectable indoor units differs
based on the height difference between the indoor units.
• When the height difference between the indoor units is 15 m or less: Up to 70~135 % of the capacity code
(Equivalent to HP) of the outdoor unit (Equivalent to HP) of the outdoor unit
• When the height difference between the indoor units is over 15 m: Up to 70~105 % of the capacity code
Follower
Follower
unit B
unit C
(10)
(1)
(1)
(5)
(4)
(9)
(7)
(7)
(4)
(4)
First branch
(4)
(10) Flow selector
unit
(5)
– 12 –
(8) Branching header
(4)
(4)*2
(4)
(10)
(5)
(7)
(4)*2
(7)
(10)
(4)
(4)*2
(10)
(6)
(5)
Indoor unit
(7) <Connecting multiple units (group operation)>
When connecting multiple indoor units to one flow
selector unit
(7) Y-shaped branching joint
(6)
(6)
Cooling only
Cooling only
(7)
(6)
(6)
24-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents