A) Rear Exit Into Flue Using; Or Black Pipe) Or (6" Dvl Close Clearance Pipe) - New Buck Corporation COMBO COAL & WOOD STOVE Owner's Manual

For burning bituminous / anthracite coal or hard, seasoned natural wood
Table of Contents

Advertisement

A. Rear Exit Into Flue using (6" Single Wall Pipe minimum 24 ga. blued

or black pipe) or (6" DVL Close Clearance Pipe)

HOW TO LOCATE CHIMNEY EXIT, AND INSTALL
NOTE: For minimum clearances:
A-1. 6" Single Wall pipe (See Page 10, Figure 6, and Figure 7 )
A-2. 6" DVL Close Clearance pipe (See Page 11, Figure 8, and Figure 9 )
1. Before connecting these units to a
through
connector thimble meets the
the connector thimble does not meet these codes, the pass-through connector must be modified.
Connectors may pass through walls or partitions constructed of combustible material if the
connector is:
(a) Either listed for wall pass-through or is routed through a device listed for wall pass-
through and is installed in accordance with the conditions of the listing.
(b) Selected or fabricated in accordance with the conditions and clearances as stated in the NFPA-211
Code. Any unexposed metal that is used as part of a wall pass-through system and is exposed to flue
gases shall be constructed of stainless steel or other equivalent material that will resist corrosion,
softening, or cracking from flue gases at temperatures up to 1800
In addition, a connector to a masonry chimney shall extend through the wall to the
inner face or liner but not beyond, and shall be firmly cemented to masonry.
EXCEPTION: A thimble may be used to facilitate removal of the chimney connector for cleaning,
in which case the thimble shall be permanently cemented in place with high-temperature cement.
2. Once the through-the-wall thimble codes are met, simply connect the (Single Wall Pipe minimum
24 ga. blue or black pipe or DVL Close Clearance pipe) to the wall pass-through connector per
chimney manufurer's instruction.
(See Page 10) A -1. 6" Single Wall pipe.
(See Page 11) A -2. 6" DVL Close Clearance pipe.
(a) Maintain 1/4" rise per foot (horizontal length) from the appliance to the chimney.
(b) Connect each section so the crimped end faces towards stove.
(c) Secure each section to each other using at least three (3) sheet metal screws or rivets, using furnace
cement to seal joints.
(d) Use three (3) sheet metal screws to fasten pipe to collar on rear of heater.
masonry
chimney, determine that the masonry flue
NFPA-211 Code and local building codes.If
Page 10
o
F.
pass-

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents