When The Louver Does Not Operate - Heat Controller B-MMC09FA-1 Service Manual

Wall mounted multi-split system air conditioning/heat pump
Hide thumbs Also See for B-MMC09FA-1:
Table of Contents

Advertisement

Troubleshooting Guide

When the louver does not operate.

Trouble 5
When Vertical Louver does not operate.
• Confirm that the Vertical Louver is normally geared with the shaft of
Stepping Motor.
• If the regular torque is detected when rotating the Vertical Louver with
hands
• Check the connecting condition of CN-UP/DOWN Connector
• Check the soldering condition(on PWB) of CN-UP/DOWN Connector
• Confirm that there is DC + 12V between pin (RED) of CN-UP/DOWN and
GND.
• Confirm that there is a soldering short at following terminals.
- Between
- Between
- Between
- Between
• Confirm the assembly conditions that are catching and interfering parts in
the rotation radial of the Vertical Louver
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Normal
Check the operating circuit of the Vertical Louver
,
,
and
of MICOM
60
61
62
63
,
,
and
of IC01M
2
3
4
5
,
,
,
of IC01M
12
13
14
15
,
,
,
and
of CN-UP/DOWN
1
2
3
4
5
If there are no problems after above checks
- 70 -
LGE Internal Use Only