Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. Table of Contents 1. PRECAUTION ........................2 1.1 Safety precaution ......................2 1.2 Warning .........................2 1.3 Caution ..........................2 2. FEATURES AND PANEL .......................3 2.1 Features ........................3 2.2 Control panel illustration ....................3 3. UNIT DIMENSION ........................6 3.1 Unit dimension: ......................6...
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. 1. PRECAUTION 1.1 Safety precaution To prevent injury to the user and property damage, the following instructions must be followed. Incorrect operation may cause harm or damage. Before servicing unit, be sure to read this service manual.
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. 2. FEATURES AND PANEL 2.1 Features Slide-in and Top-out chassis for simple installation and service (on some models). Washable one-touch filter and easy access panel. Super compact design.
Page 5
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. Control panel for cooling and heating models: B Panel Note: The control panels above are representative of many available models. Your model may be slightly different. On/Off (On and Off): Press this button once to start the unit, press again to stop.
Page 6
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. TIMER: Press this button to set the time for unit starting or stopping. Press or hold the Up (▲) / Down (▼) to set the timer time. Turning the unit ON or OFF at any time will cancel the Auto Start/Stop function.
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. 3. UNIT DIMENSION 3.1 Unit dimension: 4. OPERATION LIMITS 4.1 Cooling operation Outdoor unit air temp DB Indoor air temp DB...
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. Note: The chart is the result from the continuous operation under constant air temperature conditions. However, the initial pull-down stage is not included. 4.2 Electric heating operation Indoor air temp DB...
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. 5. PROTECTION FUNCTION 5.1 Symbol & Meaning TA: Indoor ambient temperature; TE: Indoor evaporator temperature; TS: Setting temperature through the remote controller. 5.2 Protection Function 3 minute compressor time delay The compressor will wait for 3 minutes before restarting, so as to prevent the pressure imbalance in refrigerant system from resulting in compressor rotor locking.
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. Fault Code Defect code Defect explanation Evaporator de-frosting defect. Indoor ambient temperature sensor failure in heating, cooling, dry and auto mode. DAHT sensor failure in heating mode. Sensor disconnection malfunction in fan only mode Sensor short circuit malfunction in fan only mode 6.
Page 11
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. CHECKING COMPRESSOR EFFICIENCY The reason for compressor inefficiency is normally due to broken or damaged suction and/or discharge valves, reducing the ability of the compressor to pump refrigerant gas. This condition can be checked as follows: 1.
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. CHECKING THE INTERNAL OVERLOAD (see Figure 4.) 1. With no power to unit, remove the leads from the compressor terminals. 2. Using an ohmmeter, test continuity between terminals C-S and C-R. If not continuous, the compressor overload is open and the compressor must be replaced.
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. compressor (HERM) terminal. A satisfactory capacitor will cause a deflection on the pointer, then gradually move back to infinity. 4. Reverse the leads of the probe and momentarily touch the capacitor terminals. The deflection of the pointer should be two times that of the first check if the capacitor is good.
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. 6.6 VALVE, DRAIN PAN (see Figure 7) During the cooling mode of operation, condensate which collects in the drain pan is picked up by the condenser fan blade and sprayed onto the condenser coil. This assists in cooling the refrigerant plus evaporating the water.
Page 15
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. HERMETIC COMPONENT REPLACEMENT The following procedure applies when replacing components in the sealed refrigeration circuit or repairing refrigerant leaks. (Compressor, condenser, evaporator, capillary tube, refrigerant leaks, etc.) 1. Recover the refrigerant from the system at the process tube located on the high side of the system by installing a line tap on the process tube.
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. side in small increments while operating the unit. 12. Restart unit several times after allowing pressures to stabilize. Pinch off process tubes, cut and solder the ends. Remove pinch off tool, and leak check the process tube ends.
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. 7. WIRING DIAGRAM The wiring diagrams listed below are representative of models deployed with full features. Your model may not offer all these features, accordingly it will slightly differ from your wiring diagram in these optional features area.
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. 8. TROUBLESHOOTING In general, problems are classified by three types. One is called Starting Failure which is caused from an electrical defect, another is ineffective Air Conditioning caused by a defect in the refrigeration circuit and improper application, and the other is called Structure Damage.
Page 19
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. The "filter check" lamp is on. Press "filter check" button several times and check whether the problem stops. Replace the main control board. Button of remote controller doesn’t work. Check the power supply.
Page 20
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. Operation panel doesn’t work. Check the power supply. Press the "LED" button of remote controller several times and check whether the problem stops. Check the wiring of display board. Repair the wiring.
Page 21
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. Display keeps showing "Ed". Check whether the evaporator frosts. Check whether the indoor air inlet is blocked. Check whether the indoor ambient temperature is too low. Check whether the indoor dust filter is too dirty.
Page 22
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. Compressor doesn’t work. Check whether the indoor temperature is lower than 59F (15°C). Check the power supply. Check whether the voltage is too high or too low. Check the wiring.
Page 23
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. The fan motor doesn’t work. Check the power supply. Check whether the indoor (outdoor) fan is locked. Check the wiring. Check whether the relays on PCB for motor work normally.
Page 24
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. The air conditioner doesn’t work. Check the power supply. Check the wiring. Check whether the transformer has failed. Measure the output voltage of transformer and check whether it is the range from +5V to 12V. If not, replace the transformer.
Page 25
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. The compressor cycles on/off frequently. Check whether the airflow is blocked. Check if the fan motor isn’t working. Check whether capacitor of compressor is working normally. Check whether the relay of compressor on PCB works normally.
Page 26
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. Water drips from the unit. Check whether the ambient humidity is too high. Check whether the indoor outlet airflow foam is wet if water is dripping from the louvers. Check whether the unit is correctly installed.
Page 27
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. Not heating or not heating enough. (Cooling and Electric Heater) Check the mode. Check whether the airflow speed is too low. Check the heat load of the room. Check the specification of PTC-heater.
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. 8.2 General Troubleshooting PROBLEM P OSSIBLE CAUSE REMARK Check voltage at electrical outlet. Correct if No power none. Check voltage at the power cord terminal. Power supply cord Replace the power cord if none.
Page 29
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. PROBLEM P OSSIBLE CAUSE REMARK Air filter Clean or replace if restricted. Vent door Close if open. Determine if the unit is properly sized for Unit undersized the area to be cooled or heated.
Page 30
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. PROBLEM P OSSIBLE CAUSE REMARK Check the voltage. Call an electrician if not No power within correct limits of +/- 10% of nominal voltage rating required. Wiring Check terminals. Repair and correct if loose.
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. 8.3 Troubleshooting Cooling PROBLEM POSSIBLE CAUSE TO CORRECT Compressor Low voltage. Check for voltage at compressor. 115 volt does not run. and 230 volt units will operate at 10% voltage variance Thermostat not set cold enough Set thermostat to coldest position.
Page 32
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. PROBLEM POSSIBLE CAUSE TO CORRECT Unit does Fuse blown or circuit tripped. Replace fuse, reset breaker. If repeats, not run. check fuse or breaker size. Check for shorts in unit wiring and components.
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. PROBLEM POSSIBLE CAUSE TO CORRECT Compressor Overload inoperative. Opens too Check operation of unit. Replace overload if attempts to soon. system operation is satisfactory. start, or runs Compressor attempts to start...
Page 34
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. PROBLEM POSSIBLE CAUSE TO CORRECT Fan motor Defective motor. Check and replace. does not Open or shorted capacitor. Replace capacitor and check. operate in Condenser fan frozen to Chassis. Check if drain pan valve is open. If not, "Constant"...
Service Manual Room Air Conditioner with R-410A Heat Controller, Inc. 9. INSTALLATION ACCESSORY LIST ▌ Part list for CD Series: Part No. Part Name Quantity 202921890000 Grille(Aluminum) 201121890009 Grille(plastic) 201121890006 Stuffer seal 201121890007 Trim Frame(side legs) 201121890008 Trim Frame(top & bottom legs) 10.