Troubleshooting Guide
Error
code
44
Outdoor air sensor
45
Condensor pipe sensor
47
D-Pipe sensor
❑ Check Point
1. Estimate the resistance of each sensor.(Unplugged)
2. Estimate the voltage of each sensor.(Plugged)
3. If the resistance is 0V or 5Vdc, then sensor is abnormal
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Title
Cause of error
• Open / Short
• Soldered poorly
• Internal circuit error
• Open / Short
• Soldered poorly
• Internal circuit error
• Open / Short
• Soldered poorly
• Internal circuit error
Check the resistance
Check point & Normal condition
Normal resistor : 10KΩ / at 25°C(77°F) (Unplugged)
Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)
Normal resistor : 5KΩ/ at 25°C(77°F) (Unplugged)
Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)
Normal resistor : 200KΩ/ at 25°C(77°F) (Unplugged)
Normal voltage : 4.5Vdc / at 25°C(77°F) (plugged)
- 74 -