(d) Installation of indoor unit
(i)
Install the indoor unit on the mounting plate.
Hook the upper part of the indoor unit on the stoppers disposed at the upper part of the mounting plate and lightly push the
lower part of the indoor unit so that the unit is fixed in position.
¡ When removing the indoor unit
1) Disconnect the lid at right and left.
2) Pull down the stoppers (right and left) pro-
vided at the bottom of the indoor unit base.
(See the detail view shown at right.)
(ii) Be sure not to leave any trap on the drain pipe.
Declining slope

(3) Installation of outdoor unit

(a) Installation of outdoor unit
(i)
Make sure that sufficient space for installation and service is secured.
(ii) Fix the leg sections of the unit on a firm base which will not play.
Attach cushion pads, etc. between the unit and the mounting fixtures not to transmit vibration to the building.
(iii) Attach a drain elbow, etc. under the drain port of the bottom plate to guide drain water.
(Drain elbow should not be used where days when temperature drops below 0°C continue for several days. Draining may be
disturbed by frozen water.)
(iv) When installing the unit at a higher place or where it could be toppled with strong winds, secure the unit firmly with
foundation bolts, wire, etc.
(b) Connection of indoor and outdoor connecting wiring
(i)
Connect the wiring according to the number of the indoor terminal block. (Mis-wiring may cause the burning damage, and
make sure to connect correctly.)
Notes (1) To prevent the mis-operation by noise, when the connecting wire too long for indoor and outdoor. Please hide the fixed wire in the pipe or use vinyl tape to set.
Do not put wire into the unit.
(2) Please let the anchorized personal to decide by indoor wiring code whether connect the leakage breaker or not.

(4) Refrigerant piping

(a) Preparation
Keep the openings of the pipes covered with tapes etc. to prevent dust, sand, etc. from entering them.
Indoor unit side
(Do not
turn)
¡ Remove the flared nuts.
(on both liquid and gas sides)
Inverted slope
Outdoor unit side
Remove
¡ Remove the flared nuts.
(on both liquid and gas sides)
Trap
1 Brown
2 Blue
3 Black
Yellow/Green
Press
Remove
¡ Install the removed flared nuts to the pipes to be connected,
then flare the pipes.
166
-
-
Light push
Indoor unit base bottom stopper
(2 places at right, left)
For power supply, indoor outdoor
Connecting wiring
Indoor/outdoor signal wire (Low voltage)
Earth wiring terminal
Dimension A
Liquid side
(φ6.35):
9.1 dia
Gas side
(φ9.52):
13.2 dia
(φ12.7):
16.6 dia
Mounting
plate
Wall