(6) Comfortable timer setting

If the timer is set at ON when the operation select switch is set at the cooling or heating, or the cooling or heating in auto mode operation
is selected, the comfortable timer starts and determines the starting time of next operation based on the initial value of 15 minutes and the
relationship between the room temperature at the setting time (temperature of room temperature sensor) and the setting temperature.
(Max. 60 minutes)
Operation mode
3 < Room temp. – Setting temp.
At cooling
3 < Setting temp. – Room temp.
At heating
Notes (1) At 5 minutes before the timer ON time, operation starts regardless of the temperature of the room temperature sensor (Th1).
(2) This function does not operate when in the Dry or Auto Dry and FAN mode.
However, the operation in item (1) does operate in the Auto Dry and FAN mode.
(3) During the comfortable timer operation, both the RUN light and TIMER light illuminate and the TIMER light goes off after expiration of the timer, ON setting
time.
(Example) Heating
Setting temperature
Room temperature

(7) Sleep timer operation

Pressing the SLEEP button causes the temperature to be controlled as shown in the following chart with respect to the set temperature.
Cooling, DRY
+ 1.0
Temperature
0
setting (˚C)
-1.0
Timer operation
(time)
Operation start time correction value (Min.)
+5
+5
Operation starting time
Time
15 min.
10 min.
earlier
earlier
0
1.0
2.0
Start
= <
1 < Room temp. – Setting temp.
3
No change
= <
2 < Setting temp. – Room temp.
3
No change
Corrects the starting time of next operation by
calculating the temperature difference.
¡ If the difference (= Setting temperature – Room tempera-
5 min.
Setting time
earlier
Heating
Temperature
setting (˚C)
-1.0
-2.0
-3.0
-6.0
Timer operation
(time)
82
-
-
Room temp. – Setting temp. 1
–5
Setting temp. – Room temp. 2
–5
ture) is 4ºC, the correction value is found to be +5 min-
utes from the table shown above so that the starting time
of next operation is determined as follows:
15 min. earlier + 5 min. = 20 min. earlier
Current operation
Correction value
start time
0
0
0.5
1.0
Start
= <
= <
2.0