Stop Mode - Mitsubishi Heavy Industries SRK20ZD-S1 Technical Manual

Hide thumbs Also See for SRK20ZD-S1:
Table of Contents

Advertisement

(14) Stop mode

Functional
Operation
components
ON
Compressor
OFF
ON
Outdoor unit fun
OFF
ON
4-way valve
OFF
ON
Indoor unit fun
OFF
Fully closed
Flap
Set location
EEV
150 pulse
EEV
control
When the complete stop command given, when
there is and abnormal stoppage command
Cooling,cooling
oriented dehumidifying
3 min.
1 min.
2 min.55 sec.
470 pulse
Stop instructions
All stop
Stop instructions
Heating,heating
Cooling,cooling
oriented dehumidifying
oriented dehumidifying
3 min.
1 min.
1 min.
2 min.55 sec.
470 pulse
Stop
All stop
instructions
232
-
-
When stoppage occurs due to thermostat operation,
switching operations and protective function operations
Heating,heating
oriented dehumidifying
2 min.55 sec.
2 min.55 sec.
1 min.
Hot keep
1st speed
470 pulse
Restart
Stop instructions
1 min.
20 sec.
470 pulse
Restart