(4) Main differences and compatibilities with the FR-F500(L) series
Item
Simple mode parameters 61
Pr. 0 Torque boost initial value
00250 to 01160:2%
User group 1 (16), user group 2 (16)
(Pr. 160, Pr. 173 to Pr. 175)
Changed/cleared
User initial value setting (Pr. 199)
functions
Intelligent optimum acceleration/deceleration
(Pr. 60 setting "3" and Pr. 61 to Pr. 63)
Automatic torque boost
(Pr. 38, Pr. 39)
Performing parameter clear and all clear (H5A96,
HAA99) with the FR-A7ND clears Pr. 345 and Pr. 346.
Advanced PID (pump function)
Pr. 500 to Pr. 516
Terminal block
Removable terminal block
PU
FR-PU04, DU04
Computer link, relay output option
Plug-in option
FR-A5NR
Three boards can be mounted
FR-F740-00023 to 00083, 00170, 00470, 00770 to 01160 are compatible in mounting dimensions
Installation size
Appendix 1-2 Replacement of the FR-A100 <EXCELENT> series

Instructions for installation

•• When using the installation holes of the FR-A100(E) series, FR-A5AT (intercompatibility attachment) is necessary.
For customers who are replacing the conventional model with this inverter
FR-F500(L)
Dedicated plug-in option (not compatible)
For other capacities, an optional intercompatibility attachment (FR-AAT) is necessary.
FR-F700
Simple mode parameters 15
Pr. 0 Torque boost initial value
initial value
00250 to 00770: 2%, 00930, 01160: 1.5%
(When the torque boost value of the FR-F500 series used
was the initial value, it is not necessary to change the
torque boost value from the initial value when replacing
with the FR-F700 series.)
User group (16) only
Setting methods were partially changed
(Pr. 160, Pr. 172 to Pr. 173)
"User initial value setting" (Pr. 199) was cleared
Substitutable with the copy function of the operation panel
(FR-DU07)
Function was cleared
For deceleration time, overvoltage fault can be avoided
with regeneration avoidance function (Pr. 882 to Pr. 885).
Automatic torque boost was cleared because of addition of
"Simple magnetic flux vector" (Pr. 80)
Pr. 345 and Pr. 346 are not cleared.
Parameter number change
Pr. 575 to Pr. 591
Removable terminal block
Upward compatibility (Terminal block of the F500 can be
mounted)
FR-PU07
FR-DU07
FR-DU04 unavailable (Partly restricted when the FR-PU04
is used. Refer to page 320.)
Built into the inverter
(RS-485 terminal, relay output 2 points)
One board can be mounted
321