Monitor display and monitor output signal
(4) Cumulative power monitor and clear (Pr. 170, Pr. 891)
On the cumulative power monitor (Pr. 52 = "25"), the output power monitor value is added up and is updated in 1h
increments.
The
operation panel (FR-DU07), parameter unit (FR-PU04
communication option)
Operation Panel
Range
0 to 99.99kWh
0.01kWh
100.0 to 999.9kWh
0.1kWh
1000 to 9999kWh
*1
Power is measured in the range 0 to 9999.99kWh, and displayed in 4 digits.
When the monitor value exceeds "99.99", a carry occurs, e.g. "100.0", so the value is displayed in 0.1kWh increments.
*2
Power is measured in the range 0 to 99999.99.99kWh, and displayed in 5 digits.
When the monitor value exceeds "999.99", a carry occurs, e.g. "1000.0", so the value is displayed in 0.1kWh increments.
The monitor data digit can be shifted to the right by the number of Pr. 891 settings.
For example, if the cumulative power value is 1278.56kWh when Pr. 891 = "2", the PU/DU display is 12.78 (display
in 100kWh increments) and the communication data is 12.
If the maximum value exceeded at Pr. 891 = "0 to 4", the power is clamped at the maximum value, indicating that a
digit shift is necessary. If the maximum value exceeded at Pr. 891 = "9999", the power returns to 0 and is recounted.
If the maximum value is exceeded at Pr. 891 = "9999", the power returns to 0 and is recounted.
Writing "0" in Pr. 170 clears the cumulative power monitor.
REMARKS
If "0" is written in Pr. 170 and Pr. 170 is read again, "9999" or "10" is displayed.
(5) Cumulative energization time and actual operation time monitor (Pr. 171, Pr. 563, Pr. 564)
On the cumulative energization time monitor (Pr. 52 = "20"), the inverter running time is added up every hour.
On the actual operation time monitor (Pr. 52 = "23"), the inverter running time is added up every hour. (Time is not
added up during a stop.)
If the numbers of monitor value exceeds 65535, it is added up from 0. You can check the numbers of cumulative
energization time monitor exceeded 65535h with Pr. 563 and the numbers of actual operation time monitor
exceeded 65535h with Pr. 564.
Writing "0" in Pr. 171 clears the actual operation time monitor. (Energization time monitor cannot be cleared.)
REMARKS
The actual operation time is not added up unless the inverter is operated one or more hours continuously.
If "0" is written in Pr. 171 and Pr. 171 is read again, "9999" is always displayed. Setting "9999" does not clear the actual operation
time meter.
(6) You can select the decimal digits of the monitor (Pr. 268)
As the operation panel (FR-DU07) display is 4 digits long, the decimal places may vary at analog input, etc. The
decimal places can be hidden by selecting the decimal digits.
In such a case, the decimal digits can be selected by Pr. 268.
Pr. 268 Setting
9999 (initial value)
No function
When 1 or 2 decimal places (0.1 increments or 0.01 increments) are monitored, the decimal places are
0
dropped and the monitor displays an integer value (1 increments).
The monitor value of 0.99 or less is displayed as 0.
When 2 decimal places (0.01 increments) are monitored, the 0.01 decimal place is dropped and the
1
monitor displays the first decimal place (0.1 increments).
When the monitor display digit is originally in 1 increments, it is displayed unchanged in 1 increments.
REMARKS
The number of display digits on the cumulative energization time (Pr. 52 = "20"), actual operation time (Pr. 52 = "23"), cumulative
power (Pr. 52 = "25") or cumulative saving power monitor (Pr. 52 = "51") does not change.
Parameters referred to
Pr. 37 Speed display, Pr. 144 Speed setting switchover
Pr. 55 Frequency monitoring reference, Pr. 56 Current monitoring reference
130
display units and display ranges are as indicated below.
Parameter Unit
*1
Unit
Range
0 to 999.99kWh
1000.0 to 9999.9kWh
1kWh
10000 to 99999kWh
Refer to page 125
/FR-PU07
) and communication (RS-485 communication,
*2
Unit
Pr. 170 = 10
0.01kWh
0.1kWh
0 to 9999kWh
1kWh
Description
Refer to page 131
Communication
Range
Unit
Pr. 170 = 9999
0 to 65535kWh
1kWh
(initial value)