Selection of operation mode and
operation location
(6) Switching of command source by external terminal (X67)
In Network operation mode, the command source switching signal (X67) can be used to switch the start command
source and speed command source. This signal can be utilized to control the signal input from both the control
terminal and communication.
Set "67" in any of Pr. 178 to Pr. 189 (input terminal function selection) to assign the X67 signal to the control terminal.
When the X67 signal is off, the start command source and speed command source are control terminal.
X67 Signal State
No signal assignment
ON
OFF
REMARKS
The ON/OFF state of the X67 signal is reflected only during a stop. It is reflected after a stop when the terminal is switched while
the inverter is running.
When the X67 signal is off, a reset via communication is disabled.
CAUTION
Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may affect the other functions. Please
make setting after confirming the function of each terminal.
Parameters referred to
Pr. 28 Multi-speed input compensation selection
Pr. 59 Remote function selection
Pr. 79 Operation mode selection
188
Start Command Source
According to Pr. 338
Command is valid only from control terminal signal.
Refer to page 86.
Refer to page 87.
Refer to page 175.
Speed Command Source
According to Pr. 339