Frequency setting by analog input (terminal 1, 2, 4)
(c) Method to adjust only the frequency without adjustment of a gain voltage (current).
(When changing the gain frequency from 50Hz to 60Hz)
Operation
1.
(Pr. 126) appears.
2.
Press
to show the present set value.
(50.00Hz)
3.
Turn
to change the set value to
"
". (60.00Hz)
4.
Press
to set.
5.
Mode/monitor check
Press
twice to choose the
monitor/frequency monitor.
6.
Apply a voltage across the inverter
terminals 2-5 (across 4-5) and turn on the
start command (STF, STR).
Operation starts at 60Hz.
REMARKS
Changing C4 (Pr. 903) or C7 (Pr. 905) (gain adjustment) value will not change the Pr. 20 value. The input of terminal 1 (frequency
setting auxiliary input) is added to the speed setting signal.
For the operating procedure using the parameter unit (FR-PU04/FR-PU07), refer to the FR-PU04/FR-PU07 instruction manual.
When setting the value to 120Hz or more, it is necessary to set Pr. 18 High speed maximum frequency to 120Hz or more. (Refer to
page 76)
Make the bias frequency setting using calibration parameter C2 (Pr. 902) or C5 (Pr. 904). (Refer to page 163)
Be cautious when setting any value other than "0" as the bias frequency at 0V (0mA). Even if a speed command
is not given, merely turning on the start signal will start the motor at the preset frequency.
Parameters referred to
Pr. 20 Acceleration/deceleration reference frequency
Pr. 73 Analog input selection, Pr. 267 Terminal 4 input selection
Pr. 79 Operation mode selection
166
Pr. 125) or
Flicker...Parameter setting complete!!
CAUTION
Refer to page 90
Refer to page 155
Refer to page 175
Display
or
Terminal 2 input
Terminal 4 input
Terminal 2 input Terminal 4 input