Setting Conditions for Communications with Host by Using Memory Switches
6-7-1

About Communications Conditions

Items Set for
Communications
Conditions
Setting Item
Comm. A Method
Set the communications method used at serial
port A. Depending on the communications
method, further communications condition set-
tings may be necessary.
Comm. B Select
Set whether serial port B is to be used for RS-
232C or RS-422A communications.
Comm. B Method
Set the communications method used at serial
port B. Depending on the communications
method, further communications condition set-
tings may be necessary.
The following settings are made for the communications conditions for com-
munications between the NT31/NT31C and the host.
Port Communications Method/Communications Type Settings
Function
Communications Condition Settings for The Host Link Method
Setting Item
Comm. Speed
Sets the communications speed
(for host link only)
for communications with the host.
Communications Condition Settings for The NT link (1:1) Method
No further communications conditions need to be set.
Communications Conditions Settings for The NT Link (1:N) Method
Setting Item
Unit No.
Set the unit number of the NT31/
NT31C.
(for NT link (1:N) only)
Comm. Speed
Sets the communications speed
for communications with the host.
Setting The Conditions for Communications with The Memory Link
Method
Setting Item
Data bits
Set the data bits length.
Stop bits
Set the stop bits length.
Parity
Set the parity.
Comm. Speed
Set the communications speed for
communications with the host.
Flow control
Set the flow control and its
method.
Response
Set whether the response is car-
ried out for normal process of
communications command or not.
Setting Options
A system program for OMRON model.
None/Host Link/NT Link (1:1)/
NT Link (1:N) (standard or high-
speed)/Bar-Code Reader
Memory link
RS-232C/RS-422A
A system program for OMRON model.
None/Host Link/NT Link (1:1)/
NT Link (1:N) (standard or high-
speed)
Memory link
Function
9600 bps/
19200 bps
Function
0 to 7
Standard or
high-speed
Function
7, 8 bits
1, 2 bits
None, even, odd
1200, 2400,
4800, 9600,
19200, 38400
bps
None, RS/CS,
XON/XOFF
Yes, No
Section 6-7
Page
161
163
164
189
166
168
161
163
164
166
Setting
Page
Options
161
Setting
Page
Options
164
Setting
Page
Options
166
159

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nt31c

Table of Contents