Dhw" Group - Viessmann VITOTRONIC 300 Installation And Service Instructions Manual

Type gw5b & mw1b, digital boiler control unit & weather-compensated digital cascade control unit
Table of Contents

Advertisement

Vitotronic 300, GW5B & MW1B Installation and Service
"Cascade" Group
Coding in the factory set condition
43:31
No ECO threshold boiler 3.
44:31
No ECO threshold boiler 4.
45:60
Start integral threshold set to 60 K x min.
46:40
Stop integral threshold set to 40 K x min.
47:15
Stop differential set to 15 K.
48:35
Do not adjust.
49:40
Do not adjust.

"DHW" Group

Coding in the factory set condition
55:0
DHW tank heating, hysteresis ± 2.5 K.
56:0
Set DHW temperature adjustable from 50 to
140° F (10 to 60° C).
58:0
Without auxiliary function for DHW heating.
59:0
DHW tank heating:
Set start point –2.5 K
Set stop point +2.5 K
5A:0
For DHW heating:
The set supply temperature is determined
by the highest system supply temperature
demand.
60:20
During DHW heating, the common supply
temperature is max. 20 K higher than the set
DHW temperature.
61:1
The circulation pump for DHW tank heating is
started immediately.
(continued)
Possible change
43:−30
ECO threshold boiler 3 adjustable from
to
-22 to +86° F (−30 to +30° C).
43:+30
44:−30
ECO threshold boiler 4 adjustable from
to
-22 to +86° F (−30 to +30° C).
44:+30
45:1
Start integral threshold adjustable from 1 to
to
255 K x min.
45:255
Note: If the threshold is exceeded, one boiler
or one burner stage is switched on.
46:1
Stop integral threshold adjustable from 1 to
to
255 K x min.
46:255
Note: If the threshold is exceeded, one boiler
or one burner stage is switched off.
47:2
Stop differential adjustable from 2 to 30 K.
to
Note: One boiler or one burner stage will
47:30
be switched off if the actual supply
temperature exceeds the set supply
temperature by this value.
--
--
Possible change
55:1
Adaptive DHW tank heating enabled.
55:2
DHW tank temperature control with 2 DHW tank
temperature sensors.
55:3
DHW tank temperature control, primary store
system.
56:1
Set DHW temperature adjustable from 50 to 194° F
(10 to 95° C).
Note: Observe the max. permissible DHW
temperature.
Adjust the temperature controller "R".
58:10
Input of a second set DHW temperature,
to
adjustable from 50 to 194° F (10 to 95° C).
58:60
(observe coding addresses "56" and "63").
59:1
Start point adjustable from 1 to 10 K below set
to
value.
59:10
5A:1
For DHW heating:
The set supply temperature is determined by the
DHW tank supply temperature demand.
60:10
The differential between the common supply
to
temperature and the set DHW temperature is
60:50
adjustable from 10 to 50 K.
61:0
The circulation pump for DHW tank heating is
started depending on the boiler water temperature.
Code 2, Vitotronic 300-K
--
--
93