Viessmann VITOTRONIC 300 Installation And Service Instructions Manual page 77

Type gw5b & mw1b, digital boiler control unit & weather-compensated digital cascade control unit
Table of Contents

Advertisement

Vitotronic 300, GW5B & MW1B Installation and Service
Group 1 "General"
Coding in the factory set condition
80:6
If a fault occurs for at least
30 sec., a fault message is displayed.
88:0
Temperature displayed in °C (Celsius).
8A:175
Do Not Adjust.
8B:0
Do Not Adjust.
8F:0
Operation in the standard menu and
extended menu enabled.
Note: The respective code is only
activated when you exit the service
menu (see page 50).
93:0
Fault messages during emissions test
function/service display do not affect
central fault messages.
95:0
Do Not Adjust.
98:1
Viessmann system number (in
conjunction with monitoring several
systems via Vitocom 300).
9B:0
Do not adjust.
9C:20
Monitoring LON participants:
If there is no response from a
participant, values specified by the
control unit are used after 20 min
and a fault message is issued
9D:0
Do not adjust.
(continued)
Code 2, Vitotronic 300, GW5B
Possible change
88:0
Immediate fault message.
80:2
The minimum fault duration until a fault
to
message is issued is adjustable from
80:199
10 to 995 sec;
1 step
88:1
Temperature displayed in °F
(Fahrenheit).
--
--
8F:1
Operation in standard menu and
extended menu blocked.
8F:2
Operation enabled in the standard menu
and blocked in the extended menu.
93:1
Fault messages during emissions test
function/ service display affect central
fault messages.
95:1
98:1
System number adjustable from 1 to 5.
to
98:5
--
9C:0
No monitoring
9C:5
Time adjustable from 5 to 60 min.
to
9C:60
--
5 sec.
--
--
--
--
--
77