Viessmann VITOTRONIC 300 Installation And Service Instructions Manual page 99

Type gw5b & mw1b, digital boiler control unit & weather-compensated digital cascade control unit
Table of Contents

Advertisement

Vitotronic 300, GW5B & MW1B Installation and Service
"Heating Circuit 1", "Heating Circuit 2", "Heating Circuit 3" Group
Coding in the factory set condition
A6:36
Extended economy control disabled.
A7:0
Only for heating circuits with mixing valve:
Without mixing valve economy function.
A9:7
With pump idle time
(heating circuit pump "OFF")
(See function description on page 51).
AA:2
With output reduction by temperature sensor
aJA.
B0:0
With remote control:
Heating mode/reduced mode: weather-
compensated.
B2:8
With remote control and for the heating
circuit, operation with room temperature hook-
up must be programmed:
Room influence factor 8.
B5:0
With remote control:
No room temperature dependent heating
circuit pump logic function.
*2
Only change the code for the system circuit A1 for boilers without lower temperature limit or for the heating circuits
with mixing valve if a remote control is connected to them.
Parameter address B5:...
1
2
3
4
5
6
7
8
*2
*2
*2
With heating circuit pump logic function:
Heating circuit pump "OFF"
1 RT
> RT
actual
set
2 RT
> RT
actual
set
3 RT
> RT
actual
set
4 RT
> RT
actual
set
5 RT
> RT
actual
set
6 RT
> RT
actual
set
7 RT
> RT
actual
set
8 RT
> RT
actual
set
Possible change
A6:5
Extended economy control enabled, i.e.
to
the burner and heating circuit pump will be
A6:35
stopped and the mixing valve closed at a
variable value, adjustable between 41 to 95° F
(5 and 35° C) plus 34° F (1° C).
The base value is the adjusted outside
temperature.
This value is based on the actual outside
temperature and a time constant, which takes
the cooling down of an average building into
consideration.
A7:1
With mixing valve economy function
(extended heating circuit pump logic):
Heating circuit pump also "OFF":
- If the mixing valve has been closed for
longer than 12 min.
Heating circuit pump "ON":
- If the mixing valve changes to control
function.
- If there is a risk of frost.
A9:0
Without pump idle time.
A9:1
With pump idle time; adjustable from 1 to 15.
to
1: short idle period
A9:15
15: long idle period
AA:0
Without output reduction.
AA:1
No function.
B0:1
Heating mode: weather-compensated
Reduced mode: with room temperature hook-up
B0:2
Heating mode: with room temperature hook-up
Reduced mode: weather-compensated
B0:3
Heating mode/reduced mode: with room
temperature hook-up
B2:0
Without room influence.
B2:1
Room influence factor adjustable from 1 to
to
64.
B2:64
B5:1
Heating circuit pump logic function, see the
to
following table.
B5:8
Heating circuit pump "ON"
+ 5 K
RT
actual
+ 4 K
RT
actual
+ 3 K
RT
actual
+ 2 K
RT
actual
+ 1 K
RT
actual
RT
actual
- 1 K RT
- 2 K RT
Code 2, Vitotronic 300-K
(continued)
< RT
+ 4 K
set
< RT
+ 3 K
set
< RT
+ 2 K
set
< RT
+ 1 K
set
< RT
set
< RT
- 1 K
set
< RT
- 2 K
actual
set
< RT
- 3 K
actual
set
99